Data sheet, Manufacturer-specific pmbus, Commands – GE Industrial Solutions CP2000DC54-PE User Manual

Page 9

Advertising
background image

GE

Data Sheet

CP2000DC54-PE series dc-dc converter

Input: -40Vdc to -72Vdc; Outputs: ±54Vdc @ 2000W; 5Vdc @ 4W

August 20, 2013

©2013 General Electric Company. All rights reserved.

Page 9

Software programming of output voltage overrides the set
point voltage configured during power_up. The program no
longer looks at the ‘margin pin’ and will not respond to any
hardware voltage setting. The default state cannot be
accessed any longer unless power is removed from the DSP.
To properly hot-plug a power supply into a live backplane,

the system generated voltage should get re-configured into
either the factory adjusted firmware level or the voltage
level reconfigured by the margin pin. Otherwise, the voltage

state of the plugged in power supply could be significantly
different than the powered system.
Voltage margin range: 42V

DC

– 58 V

DC

.

A voltage programming example: The task: set the output
voltage to 50.45V

DC

The constants for voltage programming are: m = 400, b and

R = 0. Multiply the desired set point by the m constant,
50.45 x 400 = 20,180. Convert this binary number to its hex

equivalent: 20,180b = 4ED4h. Transmit the data LSB first,
followed by MSB,
0 x D44Eh.

Vout_OV_fault_limit (40h) :

This command sets the Output

Overvoltage Shutdown level.

Manufacturer-Specific PMBus

TM

Commands

Many of the manufacturer-specific commands read back

more than two bytes

.

If more than two bytes of data are

returned, the standard SMBus

TM

Block read is utilized. In this

process, the Master issues a Write command followed by

the data transfer from the power supply. The first byte of the
Block Read data field sends back in hex format the number
of data bytes, exclusive of the PEC number, that follows.
Analog data is always transmitted LSB followed by MSB. A
No-ack following the PEC byte signifies that the transmission
is complete and is being terminated by the ‘host’.

Read_status (D0h) :

This ‘manufacturer specific’ command

is the basic read back returning STATUS and ALARM register

data, output voltage, output current, and internal
temperature data in a single read.

1 8 1

8

1

S Slave

address Wr A Command

Code A

1

8

1 8 1

Sr Slave

address Rd A

Byte count = 9

A

8 1 8 1 8 1

Status-2 A Status-1 A Alarm-2 A

8

1 8 1 8 1

Alarm-1 A Voltage LSB

A

Voltage MSB

A

8 1 8

1 8 1

1

Current A Temperature A PEC NA P

Status and alarm registers

The content and partitioning of these registers is

significantly different than the standard register set in the
PMBus™ specification. More information is provided by
these registers and they are accessed rapidly, at once, using
the ‘multi parameter’ read back scheme of this document.
There are a total of four registers. All errors, 0 – normal, 1 –
alarm.

Status-2

Bit

Title

Description

7

PEC Error

Mismatch between computed and
transmitted PEC. The instruction has
not been executed. Clear_Flags
resets this register.

6

Will Restart

Restart after a shutdown = 1

5

Invalid Instruction

The instruction is not supported. An
ALERT# will be issued. Clear_Flags
resets this register.

4 Power

Capacity n/a

3 Isolation

test

failed

Information only to system controller

2

Restarted ok

Informs HOST that a successful

RESTART occurred clearing the status
and alarm registers

1

Data out of range

Flag appears until the data value is
within range. A clear_flags
command does not reset this register
until the data is within normal range.

0

Enable pin HI

State of the ENABLE pin, HI = 1 = OFF

Isolation test failed:

The ‘system controller’ has to

determine that sufficient capacity exists in the system to
take a power supply ‘off line’ in order to test its isolation
capability. Since the power supply cannot determine

whether sufficient redundancy is available, the results of this
test are provided, but the ‘internal fault’ flag is not set.

Status-1

Bit

Title

Description

7 spare

6

Isolation test OK

Isolation test completed successfully.

5

Internal fault

The power supply is faulty

4 Shutdown

3

Service LED ON

ON = 1

2

External fault

the power supply is functioning OK

1

LEDs flashing

LEDs tested test ON = 1

0

Output ON

ON = 1

Alarm-2

Bit

Title

Description

7 Fan

Fault

6

No primary

No primary detected

5

Primary OT

Primary section OT

4

DC/DC OT

DC/DC section OT

3 Output

voltage

lower than bus

Internal regulation failure

2 Thermal

sensor

failed

Internal failure of a temperature
sensing circuit

1

5V out_of_limits

Either OVP or OCP occurred

0

Power delivery

a power delivery fault occurred

Power Delivery:

The power supply compares its internal

sourced current to the current requested by the current
share pin. If the difference is > 10A, a fault is issued.