1 shunt trip, 2 charging motor, 3 remote close – GE Industrial Solutions EntelliGuard 800–2000 A Frames, 240–600 Vac User’s Guide User Manual

Page 18: 4 open-fuse lockout

Advertising
background image

EntelliGuard™ 800–2000 Ampere Power Circuit Breakers
Chapter 4. Accessory Operation

Chapter 4 contains the operation procedures for each of

the available breaker accessories.

4.1 Shunt Trip

The Shunt Trip allows the breaker to be opened remotely

by the EntelliGuard Messenger™. It is always provided on

electrically operated breakers. The catalog number and

operating voltage for the Shunt Trip are listed in Table 4.

For installation instructions see DEH168.

Catalog

Number

Voltage

Rating

WPS1SF60120 120 Vac, 60 Hz

Table 4. Catalog number and operating voltage for the Shunt Trip

accessory.

Operation

The Shunt Trip causes the circuit breaker to trip when its

coil is energized. An “A” auxiliary switch, which is closed

when the breaker is closed, is in series with the Shunt Trip

coil, as illustrated in Figure 5. The voltage source is

connected to positions 5 and 7 on the secondary dis-

connect.







Figure 5. Shunt Trip connections to the auxiliary switch and secondary

disconnect.

4.2 Charging Motor

The Charging Motor provides a means of electrically

charging the springs that close the breaker. The Charging

Motor is available only as a factory-installed option. It is

always provided on electrically operated breakers.

Operation

The circuit breaker closing springs are charged automati-

cally when control voltage is applied to terminals 8 and 17

of the secondary disconnect. When the springs are fully

charged, a cutoff switch automatically de-energizes the

motor. The closing springs will recharge automatically

after the breaker closes.

4.3 Remote Close

The Remote Close allows the breaker to be closed remotely

by the EntelliGuard Messenger™ after the closing springs

have been charged. It is always provided on electrically

operated breakers. The catalog number and operating

voltage for the Remote Close accessory are listed in Table

5. For installation instructions see DEH172.

Catalog Number

Voltage Rating

WPRCSF60120

120 Vac, 60 Hz

Table 5. Catalog number and operating voltage for the Remote Close

accessory.

Operation

A circuit breaker equipped with the Remote Close acces-

sory can be closed by applying the rated control voltage to

terminals 9 and 18 of the secondary disconnect.
The Remote Close accessory is continuously rated and has

an antipump feature that prevents a motor-operated

breaker from repeatedly closing if the closing signal is

maintained. The closing control voltage must be removed

for 1–2.5 seconds and then reapplied for each breaker clo-

sure.

4.4 Open-Fuse Lockout

The Open-Fuse Lockout, shown in Figure 6, is supplied on

integrally fused breakers or when the breaker is used in

combination with a Fuse Rollout Element. When any fuse

blows, the Open-Fuse Lockout trips the breaker to prevent

single-phasing. This accessory is available only as a factory-

installed option.

Figure 6. Open-Fuse Lockout accessory.

Operation

The Open-Fuse Lockout contains an individual trip sole-

noid for each pole, connected directly across the fuse in

that phase. When any fuse blows, its solenoid is energized

and trips the breaker. An indicator shows which fuse has

blown. The breaker is mechanically trip-free and cannot

5

7

Aux Switch

3C

3

2

1

Shunt Trip