EntelliGuard™ 800–2000 Ampere Power Circuit Breakers

Chapter 4. Accessory Operation

11

be reclosed until the blown fuse is replaced and the Open-

Fuse Lockout is reset.
The Open-Fuse Lockout is internally wired to the fuses on

800- and 1600-ampere frame breakers. On 2000-ampere

frame breakers, the Open-Fuse Lockout is wired to the

secondary disconnect as illustrated in Figure 7. The Open-

Fuse Lockout connects to the fuses in a Fuse Rollout

Element through the secondary disconnect.

Figure 7. Open-Fuse Lockout (OFLO) connections to the secondary

disconnect for EGF-20 breakers.

4.5 Bell Alarm with Lockout

The Bell Alarm with Lockout prevents closing of the

breaker after a protection trip until the Bell Alarm with

Lockout is reset. It contains a set of switch contacts to

remotely indicate that the circuit breaker has tripped

because of a protection trip. Catalog numbers for the Bell

Alarm with Lockout module and kit are given in Table 6.

For installation instructions and trouble-shooting, see

DEH238.

Kit Catalog

Number

Module Catalog

Number

EGBLALMSFKIT

EGBLALMRPLC

Table 6. Catalog numbers for the Bell Alarm with Lockout module and

kit.

Operation

The Bell Alarm with Lockout prevents reclosing of the

breaker after a trip until it is reset. The accessory is

activated and its status circuit changes state whenever the

breaker is tripped by an overcurrent, ground fault, or

protective relay function via the EntelliGuard

Messenger™. The EntelliGuard Messenger continuously

monitors the state of the status circuit. The connections of

the Bell Alarm with Lockout to the secondary disconnect

are illustrated in Figure 8. A trip caused by the manual

OPEN

button or by the Shunt Trip does not activate the

Bell Alarm with Lockout.
The Bell Alarm with Lockout can be reset by manually

depressing the yellow target/RESET button on the breaker

escutcheon. This will return the Bell Alarm with Lockout

status contact to its normal configuration and allow the

breaker to be closed.

Figure 8. Bell Alarm with Lockout connections to the secondary

disconnect. The contact is shown in the RESET state.

4.6 Network Interlock

The Network Interlock provides a means of locking out a

breaker to coordinate its operation with other breakers in

the distribution network. When activated by the

EntelliGuard Messenger™, the Network Interlock prevents

the breaker from closing. When the EntelliGuard

Messenger issues a RESET signal, the breaker is able to

close either remotely or locally. The Network Interlock

contains a set of switch contacts to remotely indicate the

state of the lockout and, thus, whether or not the breaker

can be closed. Catalog numbers and the operating voltage

for the Network Interlock are listed in Table 7. For

installation instructions and trouble-shooting, see

DEH41119. The Network Interlock accessory is only

available on electrically operated breakers.

Kit Catalog

Number

Module Catalog

Number

Voltage Rating

EGNTWKSFKIT

EGNTWKSFRPLC 120 Vac, 60 Hz

Table 7. Catalog numbers and operating voltage for the Network

Interlock accessory.

Operation

The Network Interlock consists of a set circuit, a reset

circuit, and a status circuit. The device connections to the

secondary disconnect are shown in Figure 9. Note that a

Bell Alarm with Lockout and a Network Interlock cannot

be installed concurrently in a breaker.





Figure 9. Network Interlock connections to the secondary disconnect.

22

2

1

OFLO

Phase A

23

24

4

3

OFLO

Phase B

25

26

6

5

OFLO

Phase C

27

14

2

1

Lockout

Trip Coil

6

16

4

3

Status

Contact

19

15

NI Set

Coil

20

21

NI Reset

Coil

1

3

2

16

19

4

5

NI Status

Contact