7 hidden close button – GE Industrial Solutions EntelliGuard 800–2000 A Frames, 240–600 Vac User’s Guide User Manual

Page 20

Advertising
background image

EntelliGuard™ 800–2000 Ampere Power Circuit Breakers
Chapter 4. Accessory Operation

4.7 Hidden Close Button

The Hidden Close Button is an unmarked replacement for

the normal

CLOSE

button. Hidden Close Buttons are

provided on all breakers with Network Interlock

accessories. Pressing the Hidden Close Button in the

normal manner will not close the breaker. The catalog

number is WPHIDONKIT1. For installation instructions

see DEH187.

Operation

Charge the breaker closing spring, then insert the end of a

stiff rod, with maximum diameter of 0.1 inch, through the

hole in the center of the Hidden Close Button, as illus-

trated in Figure 10. When the rod engages the mechanism,

light pressure on the rod will close the breaker mechanism.

The Hidden Close Button is double-insulated from the

current-carrying parts of the breaker.

Figure 10. Operation of the Hidden Close Button.

Advertising