EntelliGuard™ 800–2000 Ampere Power Circuit Breakers

Chapter 5. Maintenance

13

5.1 Inspection

The circuit breaker should be inspected at least once every

two years. More-frequent inspections are recommended

when the breaker is employed under unfavorable con-

ditions such as severe load, dust, moisture, a large number

of operations, or if the vital nature of the load warrants it.
Always inspect the breaker after it has interrupted a short

circuit or ground fault.

WARNING: Before inspecting the breaker, dis-

connect it from all voltage sources.

AVERTISSEMENT: Débrancher le disjoncteur

de toutes sources de courant avant de

l’inspecter.

The following checks should be made with the breaker

drawn out to the

TEST

position.

1. Manually operate the breaker several times, check-

ing for obstructions or excessive friction.

• To charge the mechanism springs, pull the oper-

ating handle down until it stops (about 90°) five

or six times. The charge indicator will show

CHARGED

on a yellow background.

• Depress the

ON

button on the front of the

breaker. The springs should discharge and, if the

latch is properly reset, the breaker will close.

2. Check electrical operation of all installed accessories

and the motor-charge system, if so equipped.

3. Remove the arc chutes, then inspect the arc chutes

and contacts for breakage or excessive burning. For

the proper procedure for removing and reinstalling

the arc chutes, see DEH203.

4. Check insulating parts for evidence of overheating

and for cracks that may indicate thermal aging.

5.2 Lubrication

Bearing points and sliding surfaces should be lubricated

with a thin film of GE Lubricant D6A15A1 (MobilGrease

28, catalog number 193A1751P1). Clean the surfaces to

be lubricated with an industry-approved solvent.
Note: Remove all excess lubricant with a clean, lint -

free cloth to avoid accumulation of dirt or dust.
The contact surfaces of the primary disconnect fingers

should be cleaned and lubricated with GE Lubricant

D6A15A1.
Note: Do not lubricate the breaker main,

intermediate, or arcing contacts or the outside

diameters of rollers. Also do not lubricate the ground

radius on the closing prop or trip latch, as this will

cause accumulation of dirt and dust.

5.3 Maintenance Publications

See DEH203 for detailed maintenance procedures and

DEF004 for available renewal parts.