GE Industrial Solutions Voltage Modules ADSVMA600D User Manual

Voltage module, Geh-6250 installation instructions, Ge energy industrial solutions

Advertising
background image

GEH-6250 Installation Instructions

Voltage Module

For Spectra

®

RMS Molded-Case Circuit Breakers with microEntelliGuard

TM

,

MicroVersaTrip

®

PM or MicroVersaTrip

®

Plus Trip Units

For Catalog Numbers ADSVMA120Y, ADSVMA208Y, ADSVMA240D,

ADSVMA277Y, ADSVMA480Y, ADSVMA480D, ADSVMA600D

Circuit Breaker Accessory

Overview
The General Electric Voltage Module is used to provide
+24Vdc Control Power to Spectra

®

RMS Molded-

Case Circuit Breakers with microEntelliGuard

TM

,

MicroVersaTrip

®

PM/Plus Trip Units via the Distribution

Cable System. The Module also provides voltage-
sensing signals to Spectra

®

RMS Molded-Case Circuit

Breakers with microEntelliGuard

TM

or MicroVersaTrip

®

PM Trip Units on the same UL Listed Circuit Breaker
Accessory Distribution Cable System. The Voltage
Module is rated 24 watts (+24Vdc @ 1.0 Amp) and
has the maximum capacity to power a Distribution
Cable System consisting of 20 Spectra

®

RMS Molded-

Case Circuit Breakers with microEntelliGuard

TM

or

MicroVersaTrip

®

PM/Plus Trip Units with a maximum

system cable length of 40 feet. The Voltage Module is
designed to operate in temperature between 0°C and
70°C.

Figure 1 shows how the Voltage Module is used in a
typical MicroVersaTrip

®

PM system. Figure 2 shows how

the Voltage Module is used in a typical MicroVersaTrip

®

Plus system. The microEntelliGuard

TM

Trip Unit can

support either configuration.

WARNING: Danger of electrical shock or injury. Turn
OFF power ahead of the switchboard before working
inside the equipment. Do not remove or install any circuit
protective devices, or any other component until the
power is turned OFF.

GE Energy

Industrial Solutions

Advertising