GE Industrial Solutions Voltage Modules ADSVMA600D User Manual

Page 10

Advertising
background image

GEH-6250 Installation Instructions

Installation and Connections
Prior to installing the Voltage Module confirm that the
module matches the voltage and system requirements
(refer back to Table 1). Also turn OFF power ahead of the
switchboard before proceeding with these instructions.

Step 1.
To install the Voltage Module into a Spectra

®

Series

Switchboard, first loosen the rail latch screws (A) and
retract latches (B) on both ends of the module as shown
in Figure 7.

Figure 7. Retracting the rail latches of a Voltage Module.

Step 2.
Then line up the guides on both ends of the Voltage
Module to notches in the Spectra

®

Series Switchboard

interior vertical rails (C) as shown in Figure 8.

Figure 8. Aligning the Voltage Module.

Step 3. Finally push inward until the Voltage Module
pressure connectors are fully engaged (plugged) into
the interior bus bars. Release the latches. The latches
will automatically lock into the interior rail when the
module is fully engaged and installed. Tighten the
rail latch screw to bolt and lock the Voltage Module
in Module pressure connectors are fully engaged
(plugged) into place as shown in Figure 9.

Figure 9. Locking the Voltage Module in place.

Once the Voltage Module is locked into place in the
switchboard, wiring to the Voltage Module interior
points should be made.

The screw terminals on the Voltage Module are labeled
by function for clarity (refer back to Figures 5A and 5B
or 6A and 6B for location information). The terminal
strip pockets on all terminals will accommodate a
spade lug or ring terminal with a tongue width up to
0.320 inches. The terminal screw size is 10-32. To make
the connections, attach an appropriate spade lug or
ring terminal to the wire, then slip the fastener beneath
the terminal screw and tighten.

The Voltage Module also contains two 12-pin plug
connectors. The connectors are keyed so they
cannot be inserted incorrectly into a mating 12-pin
receptacle connector. To connect to the Voltage
Module plugs, align the receptacle interlock connector
of a Distribution Cable Harness with the plug hook
connector of the Voltage Module. Insert the receptacle
until the interlock and hook catch (see Figure 10). To
disconnect from the Voltage Module, press down at the
rear of the receptacle interlock until the interlock clears
the plug hook and withdraw the receptacle interlock
(see Figure 11).

Advertising