GE Industrial Solutions Voltage Modules ADSVMA600D User Manual

Page 4

Advertising
background image

GEH-6250 Installation Instructions

The Voltage Module contains both a Power Supply
Plate and a Voltage Conditioner Assembly as integral
components. The module also includes fuse protection
for the AC source input terminals (see Figure 3). The
Voltage Module is available in seven ratings. Table 1
contains a listing of all GE Voltage Modules. All units are
rated 60 Hz.

Figure 3. Interior view of the Voltage Module (left side Power

Supply Plate, right side Voltage Conditioner Plate)

Table 1. GE Voltage Modules

Voltage

Rating

System

Configuration

Catalog

Number

Sensing Connection

120Vac 3f4W – Wye

ADSVMA120Y Phase to Neutral potential

208Vac 3f4W – Wye

ADSVMA208Y Phase to Phase potential

240Vac 3f3W – Delta

ADSVMA240D Phase to Phase potential

277Vac 3f4W – Wye

ADSVMA277Y Phase to Neutral potential

480Vac 3f4W – Wye

ADSVMA480Y Phase to Phase potential

480Vac 3f3W – Delta

ADSVMA480D Phase to Phase potential

600Vac 3f3W – Delta

ADSVMA600D Phase to Phase potential

A communications connection is provided for
applications where data is transmitted to an external
intelligent device (See Table 2). The distribution cable
system is used to interconnect the voltage signal on
the Voltage Conditioner Plate and the Spectra

®

RMS

Molded-Case Circuit Breakers.

CAUTION: The microEntelliGuard™ trip unit system
uses modbus communications and should never be
connected to a Commnet bus

An additional voltage output connection is available for
applications where a voltage signal is needed on an Air
Circuit Breaker or Insulated Case Circuit Breaker with an

EntelliGuard™ TU or a MicroVersaTrip

®

PM Trip Unit. (Do

not connect this voltage signal to a Spectra

®

Trip Unit.

The voltage signal structure is different between the
MCCB and ACB/ICCB Trip Unit platforms).

CAUTION: The voltage-sensing signal structure for
MicroVersaTrip

®

PM and EntelliGuard™ TU Trip Units

used in Air Circuit/Insulated Case Breakers is different
than the voltage-sensing signal structure used on
Spectra

®

RMS Breakers with MicroVersaTrip

®

PM or

microEntelliGuard™ Trip Units.

Additional 24Vdc output connections are supplied for
applications where +24Vdc control power is required
independent of the Distribution Cable System (i.e.
feeding Air Circuit Breakers and/or Insulated Case
Breakers with a MicroVersaTrip

®

PM/Plus Trip Units).

NOTE: THE VOLTAGE MODULE IS SIZED FOR A MAXIMUM
OF 20 BREAKERS. Use of the Voltage Module to provide
voltage-sensing signals and/or +24Vdc control power
to a main Air Circuit Breaker or a main Insulated Case
Breaker with a MicroVersaTrip

®

or EntelliGuard

TM

TU

Trip Unit reduces the total quantity of 20 Spectra

®

RMS

Molded-Case Circuit Breakers with microEntelliGuard

TM

or MicroVersaTrip

®

PM/Plus Trip Units by one. The overall

maximum cabling length of the system remains 40 feet.

Supplemental 24Vdc input terminals are provided
for systems that have access to an external +24Vdc
power supply. If this supplemental input is connected,
the Voltage Module will continue to pass the control
power to breakers and accessories connected to the
Distribution Cable System if the primary AC power is
lost or drops below the minimum requirement. This
backup input must meet ANSI C37.90.1 for oscillatory
and fast transient surges or damage to the Voltage
Module may result (the Voltage Module provides this
protection for the primary AC input). By plugging the
Voltage Module into the Distribution Cable System,
you create system wide signals that are available to
all Spectra

®

RMS Molded-Case Circuit Breakers with

microEntelliGuard

TM

or MicroVersaTrip

®

PM/Plus Trip

Units connected to the system; a list of available signals
appears in Table 2.