GE Industrial Solutions Voltage Modules ADSVMA600D User Manual

Page 12

Advertising
background image

GEH-6250 Installation Instructions

Step 6.
After a Spectra

®

RMS Molded-Case Circuit Breaker with

microEntelliGuard

TM

or MicroVersaTrip

®

PM/Plus Trip

Unit is mounted on a Spectra

®

Series Circuit Breaker

Module, the breaker/ mounting module assembly
can be installed in the Spectra

®

Series Switchboard.

If the breaker has a breaker cable with a 12-pin
receptacle connector, plug the breaker receptacle into
the “BREAKER” 12-pin plug connector of the nearest
Distribution Cable Junction Box.

Step 7.
Spectra

®

RMS Molded-Case Circuit Breakers with

microEntelliGuard

TM

or MicroVersaTrip

®

PM Trip Units

require one additional step. You

MUST install an

auxiliary switch (microEntelliGuard

TM

Trip Units require

an auxiliary switch with gold plated contacts) in the
right accessory pouch of the breaker and route the
red and white wires of the switch to the “AUX SWITCH”
two-screw terminal block of the junction box. The
installation of this auxiliary switch will also require that
an IX filler plate (catalog number APPIW) be installed
between every Spectra

®

RMS Molded-Case Circuit

Breaker with microEntelliGuard

TM

or MicroVersaTrip

®

PM

Trip Unit.

Another use of the junction box (independent of the
Distribution Cable System) is the connection of the
neutral current sensor to any Spectra

®

RMS Molded-

Case Circuit Breaker with a microEntelliGuard

TM

,

MicroVersaTrip

®

PM or a MicroVersaTrip

®

Plus Trip Unit

that has the equipment ground fault option.

3Ø/3W

systems need no connection in order to function

properly. Wire the black and white wires of the neutral
current sensor to the “NEUTRAL CURRENT SENSOR”
two-screw terminal block on the junction box.

Figure 12 shows a completely wired installation of a
Spectra

®

RMS Molded-Case Circuit Breaker with a

MicroVersaTrip

®

PM Trip Unit detailing an installed

Voltage Module (D), mounted Junction Box (E),
connected Distribution Cable Harness (F), breaker
connection (G), wired auxiliary switch leads (H), and
connected current sensor wires (I).

Figure 12. Voltage Module, Spectra

®

RMS Molded-Case Circuit

Breakers with MicroVersaTrip

®

PM Trip Units and Distribution

Cable Junction Boxes installed in a Spectra

®

Series Switchboard.

Step 8.
Filler plates (J) are included with the Voltage Module to
assure a dead front and install the front plate (K) to the
supports of the 1X filler plate as shown on Figure 13.