Two-Wire Connection

The two-wire connections states are shown in Figure 3.

Figure 3. Two-wire input connections.

Operation

A two-wire connection requires a jumper between

ON

and

COM

, which results in a default value of

ON

. If the switch

(AB) is open the state is

ON

and if it is closed the state is

OFF

.

Momentary Inputs

The following rules apply to momentary inputs:

• All state-changing pulses must be sustained for 100

milliseconds or more.

• A multistate (MI) object must be used to determine

which of the two states the input is in.

• This input configuration can generate two valid and

distinct states using digital values 0 and 4096,
representing 0 V and 5 V. A transition from

OFF

to

ON

state of the MI object toggles the corresponding

BV object. For example, changing the MI115 object
from

OFF

to

ON

toggles the BV115 object.

Maintained Inputs

A multistate object (MI) can be used to capture the

ON

and

OFF

states.

Viewing and Editing Switch
Status

The handheld LCD Programmer, cat. no. GLCHPK, can
be used to view and manually edit switch status. See
DEH41088, LCD Programmer Quick Start Guide, for a
description of the operation and menu sequence.

The available switches are listed in Table 2.

Object

Name

Object

Type

LINKnet

Device

Address

Expansion

Module

Comment

LTG SW

101–116

MI101–

MI116

1

Standard

Default

address

LTG SW

201–216

MI201–

MI216

2

Remote

Settable by

dip switch

LTG SW

301–316

MI301–

MI316

3

Remote

Settable by

dip switch

LTG SW

401–416

MI401–

MI416

4

Remote

Settable by

dip switch

LTG SW

501–502

MI501–

MI502

5

Remote

Settable by

dip switch

Table 2. Switch object types and addresses.

Checking Switch Status

To check switch status, first log on to the LCD
programmer, then use the up and down arrow keys to
scroll to the I/O menu:

Press the

OK

key to display the following menu:

Press the down arrow key twice to reach the lighting
switches menu:

Press

OK

to display the following menu:

The human figure indicates that the switch is not
commissioned. It does not matter whether the switch is
commissioned or not.

This display indicates that lighting switch 101 is off. Press
the up and down arrow keys to view the status of all other
available switches, as listed in Table 2.