Chapter 2. Installation & Start-up
7
2-1 Mounting Position/Required Clearances
When installing the equipment, the following criteria must be observed:
• The equipment should be installed in a vertical position to ensure proper cool air circulation.
• Do not install equipment in environments containing explosive or flammable gases.
• Equipment should be well ventilated, with minimum clearances as indicated in the following illustration:
Minimum Clearances
2-2 Installation Recommendations
It is recommended that all signal wiring be shielded wiring or twisted pairs.
Do not install capacitors to correct the power factor between the reduced voltage starter output and
the motor.
Relays and contactors located in the same housing as the reduced voltage starter should have an RC
suppressor parallel to the coil (or a reverse diode, if controlled by DC).
ASTAT-SD
2 in
50mm
6 in
150mm
4 in
100mm
2 in
50mm
+
AC
DC