ASTAT-SD

Solid-State Reduced Voltage Starters

Chapter 1. Technical Specifications

3

Inputs/Outputs (continued)

Relay output ratings

5A maximum
120VAC 360 VA pilot duty B300 & 1/3hp 45LRA 7.2FLA
240VAC 470VA pilot dutyB300 & 1/2hp 30LRA 5.0FLA
General purpose DC ratings: 24VDC 8A

48VDC 0.8A
240VDC 0.1A

Protections

Current limit

Adjustable from 200 to 500% starter rating

Loss of input phase

Trip at 3 sec

Thyristor short circuit

Trip at 200ms

Loss of output phase

Trip at 3 sec

Supply frequency error

If frequency <48Hz or >62Hz, will not start

Error (CPU)

60ms

Overload protection

Separate overload relay required

Description of terminals

1L1, 3L2, 5L3

Power supply inputs +10%, -15%

2T1, 4T2, 6T3

Outputs to motor

A1/A2, B1/B2

Command supply inputs (110/120 - 220/240V AC), +10%, -15%

11, 14

Run/End of ramp internal relay output (1NO)

1, 57

Run command input

2, 57

Stop command input

3, 4

Not used

Features

SCR repetitive peak inverse
voltage (PIV)

1600V

Transient protection -

QC2B through QC2I: 120 joules

metal oxide varistors

Standards and listings

UL 508, File E 153901
CSA 22.2/14, File LR30821
IEC 947-4-2
In conformity with EN500B-1, EN500B2-2, EN 53001,
EN 60801-2, ENV 50140,
EN 61000-4-4, EN 610004-5
Complies with Electromagnetic Compatibility Directives
89/336/EEC 5/3/89

1

Reduce rated controller current (Ir) by 1.5%°C above 45°C, maximum 55°C.

2

Reduce rated controller current (Ir) by 1%/330 feet above 3300 feet, maximum 10,000 feet
(1%/1000m above 1000m, 3000m maximum).

3

See page 9 for start time limitations.