3

SECTION 1 INSTALLING THE

WIRE HARNESS ASSEMBLY

Wire Harness Connector Assembly and
Installation

The wire harness includes a 36-pin programmer

connector, which must be assembled and installed

to the programmer bracket prior to the installation

of the programmer unit.

WARNING: THE ADAPTER BRACKET MUST BE

INSTALLED ONTO THE PROGRAMMER 36-PIN

CONNECTOR AND PROGRAMMER BRACKET AS

DETAILED BELOW. FAILURE TO DO SO WILL

RESULT IN HARNESS PLUG FAILURE AND THE

PROGRAMMER WILL NOT PROVIDE

PROTECTION. IF THE CONVERTED BREAKER IS

ENERGIZED OR PRIMARY INJECTED WITH THE

ADAPTER BRACKET NOT INSTALLED OR

INSTALLED IMPROPERLY, DAMAGE WILL

RESULT TO THE PROGRAMMER UNIT, WIRE

HARNESS, 36-PIN CONNECTOR, AND CT’S.

FAILURE TO ADHERE TO THESE INSTRUCTIONS

WILL VOID ALL WARRANTIES.

Step 1.

Slide the adapter bracket onto the 36-pin

programmer connector (Figs. 1a & 1b). Be sure

that the beveled corners of the programmer

connector are facing toward the right side, the

adapter bracket slides in place behind the notches

on either side of the connector body, and that the

connector’s tabs align with the notches provided

on the bottom of the adapter bracket.

Step 2.

Hold the adapter bracket tight to the programmer

connector and bend the two (2) locking tabs

provided on the adapter bracket over the

connector body (Fig. 1c).

Fig. 1a. 36-Pin Programmer Connector

Fig. 1b. Adapter Bracket

Fig. 1c. Adapter Bracket Locking Tabs