SECTION 2 INSTALLING THE

PROGRAMMABLE TRIP UNIT

The programmer is attached to the programmer

mounting bracket. The guide pins in the bracket

mate with the holes on either side of the

programmer box. The guide pins provide the

necessary alignment for the connector

engagement. The locking lever engages with the

pin, which is assembled to the programmer unit,

and secures the programmer to the mounting

bracket.

To Install the Programmer:

Step 1.

Insert the guide pins into the holes and push on

the programmer. This will engage the connectors

and release the locking lever which will move

upwards (Fig. 2).

Step 2.

Verify that the locking lever actually engaged with

the pin on the rear of the programmer.

To remove the programmer, pull the locking lever

down, thus releasing the programmer pin. Then,

remove the programmer.

WARNING: BE SURE TO PERFORM THE

CONTINUITY TEST DETAILED IN STEP 1 OF

TESTING ON PAGE 6 PRIOR TO ENERGIZING

OR PRIMARY INJECTING THE CONVERTED

BREAKER. FAILURE TO DO SO MAY RESULT IN

DAMAGE TO THE PROGRAMMER UNIT, WIRE

HARNESS, 36-PIN PROGRAMMER CONNECTOR

AND CT’S. FAILURE TO ADHERE TO THESE

INSTRUCTIONS WILL VOID ALL WARRANTIES.