GE Industrial Solutions MicroVersaTrip Plus and MicroVersaTrip PM AK-25 and AKU-25 User Manual

Page 7

Advertising
background image

7

SECTION 3 TESTING AND

TROUBLESHOOTING
(CONTINUED)

False Tripping Breakers Equipped with
Ground Fault

When nuisance tripping occurs on breakers

equipped with the ground fault trip element, a

probable cause is the existence of a false

“ground” signal. Each phase sensor is connected

to summing circuitry in the programmer. Under

no-fault conditions on 3-wire load circuits, the

currents add to zero, and no ground signal is

developed. This current sum will be zero only if

all three sensors have the same electrical

characteristics. If one sensor differs from the

others (i.e., different rating or wrong tap setting),

the circuitry can produce output sufficient to trip

the breaker. Similarly, discontinuity between any

sensor and the trip unit can cause a false trip

signal.

The sensors and their connections should be

closely examined if nuisance tripping is

encountered on any breaker whose
MicroVersaTrip

Plus or MicroVersaTrip

PM

components have previously demonstrated

satisfactory performance. After disconnecting the

breaker from all power sources, perform the

following steps:

Step 1.

Check that all phase sensors are the same type

(ampere range).

Step 2.

Make sure that the tap settings on all three phase

sensors are identical.

Step 3.

Verify that the harness connections to the sensors

meet the polarity constraints indicated by the

cabling diagram detailed in the installation

instructions included with the conversion kit.

Step 4.

On ground fault breakers serving four-wire loads,

check that the neutral sensor is properly

connected. Refer to the cabling diagram . In

particular, check the following:

a. Verify that the neutral sensor has the same

rating and tap setting as the phase sensors.

b. Check continuity between the neutral sensor

and its equipment mounted secondary dis-

connect block. Also check for continuity from

the breaker mounted neutral secondary dis-

connect block through the female harness

connector.

c. If the breaker’s lower studs connect to the

supply source, then the neutral sensor must

have its load end connected to the source.

Refer to the cabling diagram detailed in the

installation instructions included with the

conversion kit.

d. Make sure that the neutral conductor is

carrying only that neutral current associated

with the breaker’s load current (neutral not

shared with other loads).

Step 5.

If the preceding steps fail to identify the problem,

then measure the sensor resistance’s. Since the

phase and neutral sensors are electrically

identical, their resistance’s should closely agree.

Table 3-1. CT Resistance Values

Refer to the CT Resistance Values detailed

in the installation instructions included

with the MicroVersaTrip Plus

or PM

Conversion Kit

Advertising