Installing the Trip Unit

1. Place a lock washer and flat washer over each of the

three

1

/

4

-20 x 1

3

/

8

" screws provided and insert

through the mounting holes on the trip unit mounting
plate. From the rear of the plate, place a flat washer,
spacer, and O-ring over the screws, as shown in
Figure 27.

2. Remove the large screw from the rear of the trip unit.

Place the trip unit in position on the mounting plate,
with the 50-pin connector aligned with the opening in
the plate. Secure with the large screw, as shown in
Figure 27.

3. Insert the 50-pin female connector on the wiring

harness into the trip unit connector through the rear
of the mounting plate. Secure to the mounting plate
with the two small screws provided, as shown in
Figure 28.

4. Place the trip unit and mounting plate in position on

the support bracket mounted to the breaker. Secure
with the screws in the mounting plate into the tapped
holes in the bracket, as shown in Figure 29.

Configuring the Trip Unit

See DEH-40034 for detailed instructions for setting up
ProTrip trip units.

Figure 27. Trip unit attached to its mounting plate.

Figure 28. Harness connector attached to the trip unit.

Figure 29. Mounting the trip unit on the breaker.

Trip Unit Screw

50-Pin

Connector

Mounting

Screw

Harness

Connector

15