3. On a DB-50 breaker, remove and discard the two

1

/

2

-

13 bolts under each load terminal, as shown in
Figure 3.

On a DB-25 breaker, remove and discard the single

3

/

8

-16 bolt under each load terminal, as shown in

Figure 4.

4. Remove the electromechanical trip devices, shown in

Figure 5, from the frame and discard them. The back
frame is now ready for conversion, as shown in
Figure 6.

1

/

2

-13

Bolts

3

/

8

-16

Bolt

Figure 4. Trip unit mounting bolts to be removed from a

DB-25.

Figure 5. Electromechanical trip devices removed from

the breaker.