background image

MicroVersaTrip Plus™ and MicroVersaTrip PM™ Trip Units
Getting Started

Since this Trip Unit is available in a variety of
configurations, please take a moment to compare the
catalog number of your purchased Trip Unit with the
catalog number key below.

Example

K 3 32 LSI GD Z1 PM R

Code

Description

Function

K

WavePro

Breaker Family

8

1

2

3

4

5

800 A

1600 A

2000 A

3200 A

4000 A

5000 A

Frame Size

01

04

08

16

20

32

40

50

150 A

400 A

800 A

1600 A

2000 A

3200 A

4000 A

5000 A

Installed CT

L

S

I

Long-time

Short-time

Instantaneous

Overcurrent Protection

G

GD

Ground Fault

Ground Fault (user defeatable)

Ground fault protection

Z1

Z2

X

GF Zone-Selective Interlock

GF & ST Zone-Selective Interlock

Switchable Inst, ST, and GF

Optional protection

P

M

Protective Relays & Comm

Metering & Comm

Optional features

R

Replacement unit

Ordered as Replacement

Example – a Trip Unit with catalog number K332LSIGDZ1PMR has the following features:

• WavePro circuit breaker
• 3200 A frame
• 3200 A installed CT
• Long-time, short-time, and instantaneous overcurrent protection
• Defeatable ground-fault protection
• Ground-fault zone-selective interlock
• Protective relays, metering, and communication
• Trip Unit was ordered as a replacement