MicroVersaTrip Plus™ and MicroVersaTrip PM™ Trip Units

Chapter 2. Setup Mode

17

Band

Time Delay, sec

OFF

Disabled

1

0.10

2

0.21

3

0.35

Table 14. Lower-limit delays for ground-fault delay bands.

Figure 21. Time-current curve for ground-fault delay with

I

2

T OUT

.

Figure 22. Time-current curve for ground-fault delay with

I

2

T IN

.

Voltage-Unbalance Relay Pickup

This function compares the highest or lowest phase volt-
age with the average of all three phases and initiates a trip
if the difference exceeds the set point. The true rms volt-
age is computed for each phase. The range of set points is
from 10 to 50% of the unbalance, with an increment of
1%. The Trip Unit display is shown in Figure 23.

Figure 23. Trip Unit display for voltage-unbalance relay pickup.

Voltage-Unbalance Relay Delay

This function sets the delay time before a voltage-unbal-
ance trip occurs. The range of delays is 1 to 15 seconds, in
steps of 1 second. Choosing

OFF

disables voltage-unbal-

ance protection. The Trip Unit display is shown in Figure
24.

Figure 24. Trip Unit display for voltage-unbalance relay delay.

Current-Unbalance Relay Pickup

This function compares the true RMS current in the
highest or lowest phase with the average of all three phases
and initiates a trip if the difference exceeds the set point.
The range of set points is 10 to 50% of the unbalance, with
an increment of 1%. The Trip Unit display is shown in
Figure 25.

Figure 25. Trip Unit display for current-unbalance relay pickup.

Current-Unbalance Relay Delay

This function sets the delay time before a current-unbal-
ance trip occurs. The range of delays is 1 to 15 seconds, in
steps of 1 second. Choosing

OFF

disables current-unbal-

ance protection. The Trip Unit display is shown in Figure
26.