MicroVersaTrip Plus™ and MicroVersaTrip PM™ Trip Units

Chapter 2. Setup Mode

19

points is 10 kW to 990 kW, in steps of 10 kW. The Trip
Unit display is shown in Figure 33.

Figure 33. Trip Unit display for power-reversal relay pickup.

Power Direction Setup

This function selects the normal power flow direction for
the breaker, either from line to load or from load to line.
Figure 34 shows the setup display for normal power flow of
line to load. This direction setup also affects the sign of the
normal power metering displays.

Figure 34. Trip Unit display for power direction setup, showing line to

load.

Power-Reversal Relay Delay

This function sets the delay time before a power-reversal
trip occurs. The range of delays is 1 to 15 seconds, in steps
of 1 second. Choosing

OFF

disables power-reversal protec-

tion. The Trip Unit display is shown in Figure 35.

Figure 35. Trip Unit display for power-reversal relay delay.

Rating Plug Current Setting

The Trip Unit display for rating plug setting is shown in
Figure 36. Enter the current setting of the rating plug by
scrolling through the list with

VALUE

and pressing

ENTER

when the correct value is reached. Table 15 lists the avail-
able rating plugs for the various Trip Units.

CAUTION: Incorrect storage of this set point will result in
incorrect metering values.

ATTENTION: Si une valeur incorrecte est enregistrée
pour ce réglage, les mesures seront fausses.

Figure 36. Trip Unit display for rating plug current set point.

Breaker

Frame

Size, A

Rating Plug Options, Amps

800–2000

60, 80, 100, 125, 150, 200, 225, 250, 300, 400, 450,

500, 600, 700, 750, 800, 1000, 1100, 1200, 1500,

1600, 2000

3200

1200, 1600, 2400, 3200

4000

1600, 2000, 2500, 3000, 3600, 4000

5000

3200, 4000, 5000

Table 15. Trip Unit rating plug options.

Potential Transformer Primary Voltage

Enter the primary voltage rating of the potential trans-
former, as illustrated in Figure 37. The range of values is
120 to 600 volts, with an increment of 1 volt.

CAUTION: Incorrect storage of this set point will result in
incorrect metering values. Even if this setting is entered
remotely, it must be entered again locally.

ATTENTION: Si une valeur incorrecte est enregistrée
pour ce réglage, les mesures seront fausses. Cette valeur
doit être enregistrée locallement même dans le cas d’une
utilisation à distance avec commnet.

Figure 37. Trip Unit display for potential transformer primary voltage

set point.