Astat-xt rvss panel, Astat-xt soft starter terminal board i/o – GE Industrial Solutions ASTAT-XT RVSS PANEL User Manual

Page 15

Advertising
background image

DEH40622 - Page 7

AN BL-0350, Rev.01, 08/20/2010

ASTAT-XT RVSS PANEL

3. ASTAT-XT Soft Starter Terminal Board I/O


Any of the ASTAT-XT terminal board I/O points, which are not already in use for proper operation of the
Solid State RVSS panel, are available for customer use. The meanings and connection diagrams for these
I/O points are well described and illustrated in the ASTAT-XT User’s Guide (ED230209 ASTAT-XT User’s
Guide

) which is supplied with your panel documentation package. However there are several I/O points,

which will find frequent use in BYPASS AND NON BYPASS panel applications that they are described
below for convenience. Refer to ED230209 ASTAT-XT User’s Guide for terminal locations. Refer to section
2 and wiring diagram for details on correct connection points

1L1, 3L2, 5L3,

Connection to mains voltage up to 690V



A, B, C,

Connections for

bypass contactor / starter



2T1, 4T2, 6T3,

Connection to Motor



G,

Connection to Ground



L (1),

Control Power Phase



N (2),

Control Neutral (Return)



F (3),

Fan Control



4,

Input – STOP command, Input from a N.C. contact, To stop the motor,
disconnect Control Input voltage from terminal 4 for at least 250mSec. (no
SOFT STOP)



5,

Input – SOFT STOP command, Input from a N.C. contact, To SOFT STOP
the motor disconnect Control Input voltage from terminal 5 for at least
250Ms



6,

Input – START command, Input from a N.O. contact, To SOFT START the
motor, connect Control Input voltage to terminal 4 for at least 250mSec



7,

Programmable input – Energy Save / Slow Speed / Reset


8,

Programmable input – Dual Set / Reverse / Reset


9,

Common to terminals 4-8



15