Table A

RVSS Panels

– 230 VAC

Wire Sizes and Torque Requirements

Device

RVSS panel Hp

Rating(s)

Minimum Wire Size

Maximum Wire

Size

Required Torque

ASTAT

2 - 25Hp

#18 AWG

# 1/0 AWG

32.7 lb.in.

30 - 60Hp

# 6 AWG

250 MCM

200 lb.in.

75 - 150Hp

(1) 2/0 AWG

600 MCM

375 lb.in.

200 - 250Hp

(4) 3/0 AWG

500 MCM

375 lb.in.

Power Distribution Blocks

2 - 25Hp

#18 AWG

# 1/0 AWG

Note 1

30 - 40Hp

# 14 AWG

# 2/0 AWG

Note 1

50 - 100Hp

# 6 AWG

350 MCM

Note 1

150

# 10 (2) AWG

# 4/0 (2) AWG

Note 1

200

# 6 (2) AWG

350 (2) MCM

Note 1

250

# 4 (2) AWG

500 (2) MCM

Note 1

Control Terminal Board

2 - 250Hp

# 26 AWG

# 10 AWG

Note 1


Note (1): For unmentioned torques, Refer UL508A tables in tab "UL508A" in the same excel file
Note (2): The input and output terminals have Busbars provision for motor connections.