Astat-xt rvss panel – GE Industrial Solutions ASTAT-XT RVSS PANEL User Manual
Page 36
DEH40623 - Page 5
AN BL-0464, Rev.02, 04/15/2012
ASTAT-XT RVSS PANEL
Table B
RVSS Panels
– 460 VAC
Wire Sizes and Torque Requirements
Device
RVSS Panel Hp
Rating(s)
Minimum Wire Size
Maximum Wire
Size
Required Torque
ASTAT
5 - 50Hp
#18 AWG
# 1/0 AWG
32.7 lb.in.
60 - 125Hp
# 6 AWG
250 MCM
200 lb.in.
150 - 300Hp
(1) 2/0 AWG
600 MCM
375 lb.in.
350 - 500Hp
(4) 3/0 AWG
500 MCM
375 lb.in.
Power Distribution Blocks
5 - 50Hp
#18 AWG
# 1/0 AWG
Note 1
60 - 75Hp
# 14 AWG
# 2/0 AWG
Note 1
100 - 150Hp
# 6 AWG
350 MCM
Note 1
250 - 300Hp
# 10 (2) AWG
# 4/0 (2) AWG
Note 1
350 - 400Hp
# 6 (2) AWG
350 (2) MCM
Note 1
500Hp
# 4 (2) AWG
500 (2) MCM
Note 1
Control Terminal Board
5 - 500Hp
# 26 AWG
# 10 AWG
Note 1
Note (1): For unmentioned torques, Refer UL508A tables in tab "UL508A" in the same excel file
Note (2): The input and output terminals have Busbars provision for motor connections.