Astat-xt rvss panel – GE Industrial Solutions ASTAT-XT RVSS PANEL User Manual

Page 37

Advertising
background image

DEH40623 - Page 6

AN BL-0464, Rev.02, 04/15/2012

ASTAT-XT RVSS PANEL

Table C

RVSS Panels

– 575 VAC

Wire Sizes and Torque Requirements

Device

RVSS Panel Hp

Rating(s)

Minimum Wire

Size

Maximum Wire

Size

Required Torque

NON FUSED DISCONNECTOR

5 - 15Hp

# 14 (1) AWG

# 10 AWG

27 lb.in.

25 - 40Hp

# 10 (1) AWG

# 3 AWG

58 lb.in.

50 -60Hp

# 10 (1) AWG

# 3 AWG

58 lb.in.

75 - 125Hp

# 6 (1) AWG

# 3/0 AWG

200 lb.in.

150 - 250Hp

#2 (1) AWG

600 MCM

500 lb.in.

300Hp

#2 (2) AWG

600 MCM

500 lb.in.

400 - 500Hp

#2 (2) AWG

600 MCM

500 lb.in.

FUSED DISCONNECTOR

5 - 15Hp

# 10 (1) AWG

# 3 AWG

58 lb.in.

25 - 40Hp

# 10 (1) AWG

# 3 AWG

58 lb.in.

50 - 60Hp

# 14 (1) AWG

# 2/0 AWG

120 lb.in.

75 - 125Hp

# 6 (1) AWG

# 3/0 AWG

200 lb.in.

150 - 250Hp

#2 (1) AWG

600 MCM

500 lb.in.

300 - 400Hp

#2 AWG

600 MCM

500 lb.in.

500Hp

#2 (2) AWG

600 MCM

500 lb.in.

Circuit Breaker

5 - 75Hp

# 12 AWG

# 3/0 AWG

160 lb.in.

100 - 150Hp

# 8 AWG

350 MCM

275 lb.in.

200 - 400Hp

# 8 AWG

400 MCM

275 lb.in.

500Hp

250 MCM

500 MCM

375 lb.in.

Contactors

5 - 25Hp

# 14 AWG

# 10 AWG

16 lb. in.

30 - 60Hp

# 14 AWG

# 10 AWG

40 lb. in.

75Hp

# 10 AWG

# 2/0 AWG

60 lb. in.

100 - 125Hp

# 6 AWG

250 MCM

275 lb. in.

150 - 300Hp

# 6 AWG

350 MCM

200 lb. in.

400 - 500Hp

# 8 AWG

500 MCM

375 lb. in.

Overload Relay

5 - 25Hp

# 14 AWG

# 8 AWG

24 lb. in.

30 - 75Hp

# 10 AWG

# 3 AWG

50 lb. in.

100 - 125Hp

# 6 AWG

250 MCM

275 lb. in., Note 2

150 - 300Hp

# 6 AWG

350 MCM

200 lb. in., Note 2

400 - 500Hp

# 8 AWG

500 MCM

375 lb. in., Note 2

Continued…