Car0812fp series rectifier, Data sheet, Input: 85v – GE Industrial Solutions CAR0812FP series User Manual

Page 12: Output: 12v, Or 5 v, Control and read accuracy, Eeprom, Leds, Alarm table

Advertising
background image

GE

Data Sheet

CAR0812FP series rectifier

Input: 85V

AC

to 264V

AC

; Output: 12V

DC

@ 850W; 3.3V

DC

or 5 V

DC

@ 1A

May 2, 2013

©2013 General Electric Company. All rights reserved.

Page 12

Vin_UV_warn_limit (58):

This is another warning flag

indicating that the input voltage is decreasing dangerously
close to the low input voltage shutdown level.

Status_word (79):

returns two bytes of information. The

upper byte bit functionality is tabulated in the Status_word
section. The lower byte bit functionality is identical to
Status_byte.

Fan_speed (D7):

This register can be used to ‘read’ the fan

speed in adjustment percent (0 – 100%) or set the fan speed
in adjustment percent (0 – 100%). The speed of the fan
cannot be reduced below what the power supply requires

for its operation. The register value is the percent number, it
is not in linear format.

Invalid commands or data:

The power supply notifies the

MASTER if a non-supported command has been sent or
invalid data has been received. Notification is implemented
by setting the appropriate STATUS and ALARM registers and

setting the SMBAlert# flag.

Control and Read accuracy:

The estimates below are believed to be reasonable under
most operating conditions. However, these are typical

numbers and not hard bound values that cannot be
exceeded. In most nominal operating conditions the
returned values are significantly better than these

estimates.

Note that temperature measurements are accurate around
the shutdown limits and they get increasingly less accurate

as the temperature level decreases.

FUNCTION

ACCURACY

Vout_command ±

2%

Vout_OV_fault_limit ±

3%

Iout_OC_warn_limit

± 4% of FL

OT_warn_limit

± 5C

Vin_UV_warn_limit

± 3%

Vin_UV_fault_limit

± 3%

Read_Vin

± 3%

Read_Vout

± 2%

Read_Iout

± 4% of FL

Read_temperature

± 5C


EEPROM

The microcontroller has 96 bytes of EEPROM memory
available for the system host.

Another separate EEPROM IC will provide another 128 bytes

of memory with write protect feature. Minimum information
to be included in this separate EEPROM: model number,

revision, date code, serial number etc.

LEDs

Two LEDs are located on the front faceplate. The AC_OK LED
provides visual indication of the INPUT signal function. When the
LED is ON GREEN the power supply input is within normal design

limits.

The second LED DC/FLT is a tri-state LED. When GREEN there are no
faults and DC output is present. When AMBER a fault condition
exists but the power supply still provides output power. When RED

then a fault condition exists and the power supply does not provide

output power.

Alarm Table

Test Condition

LED Indicator

Monitoring Signals

LED1

AC

Tri-Color LED2

DC / FLT

FAULT

DC OK

INPUT OK

TEMP OK

1 Normal

Operation

Green

Green

High High High High

2

Low or NO INPUT

Off

Red

Low Low Low High

3 OVP

Green

Red

Low Low High High

4 Over

Current

Green

Red

Low Low High High

5

Temp Alarm Warning

Green

Orange

High

High High Low

6 Fault

Over

Temp

Green

Red

Low Low High Low

7 Remote

ON/OFF

Green

Red

Low Low High High

Notes: Test condition #2 had 2 modules plug in. One module is running and the other one is with no AC.