Car0812fp series rectifier, Data sheet, Input: 85v – GE Industrial Solutions CAR0812FP series User Manual

Page 9: Output: 12v, Or 5 v, Pmbus, Commands, Command set, Mv 2

Advertising
background image

GE

Data Sheet

CAR0812FP series rectifier

Input: 85V

AC

to 264V

AC

; Output: 12V

DC

@ 850W; 3.3V

DC

or 5 V

DC

@ 1A

May 2, 2013

©2013 General Electric Company. All rights reserved.

Page 9

internal processors to update their data base so that
successive reads provide fresh data.

PMBus

TM

Commands

Standard instruction:

Up to two bytes of data may follow

an instruction depending on the required data content.
Analog data is always transmitted as LSB followed by MSB.
PEC is optional and includes the address and data fields.

1 8 1

8 1

S Slave

address Wr A Command

Code A

8 1 8 1

8

1

1

Low data byte

A High

data

byte A PEC A P

Master to Slave Slave to Master
SMBUS annotations; S – Start , Wr – Write, Sr – re-Start,
Rd – Read,

A – Acknowledge, NA – not-acknowledged, P – Stop

Standard READ:

Up to two bytes of data may follow a READ

request depending on the required data content. Analog
data is always transmitted as LSB followed by MSB. PEC is
mandatory and includes the address and data fields

.

PEC is

optional and includes the address and data fields.

1 7

1

1 8 1

S Slave

address Wr A Command

Code A

1 7 1

1 8

1

Sr Slave

Address Rd A

LSB A

8 1 8

1

1

MSB A PEC No-ack

P

Block instruction:

When writing or reading more than two

bytes of data at a time BLOCK instructions for WRITE and
READ commands must be used instead of the Standard

Instructions.

Block write format:

1 7 1

1

8 1

S Slave

address Wr A Command

Code A

8 1

8

1

8

1

Byte count = N

A Data

1 A Data

2 A

8 1 8 1 8 1

1

………. A Data

48 A PEC A P

Block read format:

1 7 1

1

8 1

S Slave

address Wr A Command

Code A

1 7 1

1

Sr Slave

Address Rd

A

8 1

8

1

8

1

Byte count = N

A

Data 1

A Data 2

A

8 1 8 1 8 1 1

………. A

Data 48

A

PEC NoAck P

Linear Data Format

The definition is identical to Part II of

the PMBus Specification. All standard PMBus values, with
the exception of output voltage related functions, are
represented by the linear format described below. Output
voltage functions are represented by a 16 bit mantissa.
Output voltage has a E=9 constant exponent.

The Linear Data Format is a two byte value with an 11-bit,
two’s complement mantissa and a 5-bit, two’s complement
exponent or scaling factor, its format is shown below.

Data Byte High

Data Byte Low

Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0

Exponent

(E)

Mantissa

(M)

The relationship between the Mantissa, Exponent, and

Actual Value (V) is given by the following equation:

E

M

V

2

Where:

V is the value

M is the 11-bit, two’s complement mantissa

E is the 5-bit, two’s complement exponent

PMBus

TM

Command set:

Command

Hex

Code

Data

Byte

Function

Operation 01

1

Output

ON/OFF

ON_OFF_config

02

1

09, output ON default

Clear_faults 03

0

Clear

Status

Write_protect 10

1

Write

control

Store_default_all 11

0 Store

permanently

Restore_default_all

12 0

Reset

defaults

Capability

19

1

30h, 400kHz, SMBAlert

Vout_mode 20

1

Vout

constants

Vout_command 21

2

Set

Vout

Vout_OV_fault_limit

40

2

Set OV fault limit

Vout_OV_fault_response 41 1
Vout_OV_warn_limit

42

2

Set OV warn limit

Vout_UV_warn_limit

43

2

Set UV warn limit

Vout_UV_fault_limit 44

2

Vout_UV_fault_response 45 1
Iout_OC_fault_limit 46

2

Iout_OC_fault_response

47 1

Latch or hiccup

Iout_OC_warn_limit 4A

2

Set OC warn limit

OT_fault_limit 4F

2

OT_fault_response 50

1

Latch or hiccup

OT_warn_limit 51

2

Set OT warn limit

UT_warn_limit 52

2

UT_fault_limit 53

2

UT_fault_response 54

1

Vin_OV_fault_limit 55

2

Vin_OV_warn_limit 57

2

Set OV warn limit

Vin_UV_warn_limit

58

2

Set UV warn limit

Vin_UV_fault_limit

59

2

Set UV shutdown

Status_byte 78

1

Status_word 79

2

Status_Vout 7A

1

Status_Iout 7B

1

Status_input 7C

1

Status_temperature 7D

1

Advertising