Power Break® II Devices

Draw-Out Device Installation

1

Description

Types SSD and SHD Power Break II draw-out circuit

breakers are used in types SPS and SPH substructures, with

appropriate catalog numbers listed in Table 1. Power

Break II switches are used only with type SPH

substructures, with appropriate catalog numbers listed in

Table 2. Draw-out construction permits activation of a new

feeder, allows rapid replacement of a device, and

facilitates inspection and maintenance of the draw-out

device with no need to de-energize the entire switchboard.

Draw-Out Breaker

Substructure

SSD08X2## SPSDOS08
SHD08X2## SPHDOS08
SSD16X2## SPSDOS16
SHD16X2## SPHDOS16
SSD20X220 SPSDOS20
SHD20X220 SPHDOS20
SSD25X### SPSDOS25
SHD25X### SPHDOS25
SSD30X3## SPSDOS30
SHD30X3## SPHDOS30
SSD40X4## SPSDOS40
SHD40X4## SPHDOS40

Note: In the circuit breaker catalog number, replace “X”

with “B” for MicroVersaTrip Plus™ or MicroVersaTrip

PM™ Trip Units or with “D” for Power+™ Trip Units

Table 1. Catalog numbers of draw-out circuit breakers and

corresponding substructures.

Draw-Out Switch

Substructure

SHD08Y2## SPHDOS08
SHD16Y2## SPHDOS16
SHD20Y2## SPHDOS20
SHD25Y### SPHDOS25
SHD30Y3## SPHDOS30
SHD40Y4## SPHDOS40

Table 2. Catalog numbers of draw-out switches and corresponding

substructures.

Features

The features described below are illustrated in Figures 1,

2, and 3.
Primary Disconnects

. Primary power is fed through multiple-

finger primary disconnects when the device is in the

connected position.
Secondary Disconnects

. Control power is provided through

the secondary disconnects in the test and connected

positions only. All accessories terminate at dedicated

positions regardless of the combination of accessories

installed.

Rollers

. The rollers on the sides of the device ride on

retractable rails in the draw-out substructure for easy

installation and removal.
Draw-Out Mechanism

. A racking shaft powers a centrally

mounted screw through a chain drive into a fixed nut in

the substructure. A special speed wrench is supplied with

an integral

1

2

-inch square-drive socket to aid in

installation and removal.
Racking Shaft Wrench Lockout Plate

. This interlock prevents

engagement of the wrench when the device contacts are

closed.

Figure 1. Rear view of the Power Break® II draw-out device.

Figure 2. Left side of the device, showing the padlock accessory and

racking shaft lockout plate.

Shutter

Actuator

Primary

Disconnects

Draw-Out

Interlock

Draw-Out

Mechanism

Bypass Switch

Actuator

Secondary

Disconnects

Rollers

Draw-Out Padlock

Accessory

Cat. No. TDOPC

Racking Shaft

Wrench Lockout

Plate