Removing the device – GE Industrial Solutions Power Break II Draw-out 800-4000 Amp Frames User Manual

Page 9

Advertising
background image

Power Break® II Devices

Draw-Out Device Installation

5

Removing the Device

Use the following procedure to remove the draw-out

device from the substructure.

CAUTION: The device must be

OFF

before it is dis-

connected and removed.

ATTENTION: Le mécanisme doit être à OFF avant qu’il

ne soit débroché et déposé.

1. Engage the

1 2

-inch square end of the racking

shaft with the supplied wrench, catalog number

TDORT, as illustrated in Figure 7, and rotate the

shaft counter-clockwise to withdraw the device to the

TEST

or

DISCONNECTED

position. The compartment

position indicator is shown in Figure 8.

2. Pull the substructure rails out as far as possible until

they drop into the horizontal locked position, as

illustrated in Figure 9.

3. From the

DISCONNECTED

position, pull the device

out on the rails until the front rollers fall into the

detent, as illustrated in Figure 6.

4. The device can now be rotated about the front roller

by pulling forward, as illustrated in Figure 10, for

inspection of the rear of the device, or it can be

completely removed after attaching the Lifting Bar,

as illustrated in Figures 4 and 5.

Figure 9. Withdrawing the substructure rails.

Figure 10. Rotating the device forward for inspection.

Advertising