Advertising
background image

DEH40153

DEH40153 Rev.No.02

2

3. Remove the circuit breaker kit from its packaging and verify that all parts are

present, as given in the packing list.

4. Refer fig.no.1 to mount the breaker on interior. Place branch base for A phase [2]

adjacent to crossbar [15] as shown in fig.1 and insert the screw [7] through slot
provided to mount it to A phase main busbar. Similarly mount B phase branch
base [1] to B phase main busbar adjacent to A phase branch base and C phase
branch base [3] to C phase main busbar adjacent to B phase branch base. All
phase branch bases should be clamped to main bus using screw [7] with 60 inch
lb max-lb.

Figure 1. Installation of a SE/TED circuit breaker kit on interior, catalog number
ASPP6SE6D, into an A-Series

®

II Panelboards.

5. Mount bracket [8] on the interior rail with two screws [9] with 27-36 in-lb at the

location defined.

6. Place the conical washer [6] over the three ¼-28 x 1

3

/

8

screws [5] and insert the

screws through the holes in the top of the circuit breaker. Secure the three spools
[4] to the underside of the breaker terminals with the screws [5]. Take care to
assemble the screws to the spools as shown in Figure 1, with the tapped end of the
spool toward the breaker terminal.