GE Industrial Solutions ZBTE Series User Manual

Page 9

Advertising
background image

Zenith ZTE/ZBTE Series Operation & Maintenance Manual

Page 7

91

R

-1000

Figure 5
Example of Field Connection Diagram

Notes:

1. See Field connection wiring diagram for additional wiring details.
2. Controller inputs and outputs are field reconfigurable. “Factory Settings: indicate configuration at time of shipment.
3. From MX350 Display, go to \HOME\INPUTS or \HOME\OUTPUTS to see current configuration.
4. Record user configuration in “Field Setting” area below.

Name

Term #

Description

TB Strip

15

Connected to Source 1 (NO)

14

Connected to Source 1 (Common)

13

Connected to Source 1 (NO)

12

Connected to Source 1 (Common)

11

Connected to Source 2 (NO)

10

Connected to Source 2 (Common)

9

Connected to Source 2 (NO)

8

Connected to Source 2 (Common)

7

6

5

4

3

Engine Start – NC

2

Engine Start – Common

1

Engine Start – NO

G Input
Strip

G 7

Disconnect Switch (DS)

Factory Use
Only

G 8

Test with Load (Q2)

Factory Use
Only

G 9

Load Shed from S2 (R15)

Factory Use
Only

G 10

Bypass Xfer Time Delay to S1

G 11

Inhibit Xfer to S2 (Q3)

G 12

Inhibit Xfer to S1 (Q7)

G 13

Engine Start (SW1)

Com

+24VDC

Factory Use
Only

Name

Term #

Factory Setting

Field Setting

G Output
Strip

G 1 (NO/NC/
Common)

Load Shed from S2 (R15)

Factory Use
Only

G 2 (NO/NC/
Common)

Alternative Source Fail to Start

G 3 (NO/NC/
Common)

S1 Failure

G 4 (NO/NC/
Common)

S2 Failure to Connect

G 5 (NO/NC/
Common)

Load Control 1

Name

Term #

Description

TB Strip

12

Connected to Source 1 (NO)

11

Connected to Source 1 (Common)

10

Connected to Source 1 (NO)

9

Connected to Source 1 (Common)

8

Connected to Source 2 (NO)

7

Connected to Source 2 (Common)

6

Connected to Source 2 (NO)

5

Connected to Source 2 (Common)

4

Bypass in Source 1 (NO)

3

Bypass in Source 1 (Common)

2

Bypass in Source 2 (NO)

1

Bypass in Source 2 (Common)

3

Engine Start – NC

2

Engine Start – Common

1

Engine Start – NO

Non-Bypass ATS

Bypass ATS

Advertising