5. Plug modular connector into P5 which is located on the System Controller on the left side of the power shelf. P5 will be

labeled as PROBE TEMP and is the connector that is located under an insulator flap farthest back on the controller. See
Figure 4.

FIGURE 4: Thermal Probe Wiring to Power Shelf

6. From the front left of the shelf, on the display go to Main Menu

Status

Batteries and scroll down to Temp

Probes (n) and verify that the controller sees that a n=1 for one probe installed.


7. Verify that the system controller is configured for the type of batteries in the system (i.e. Lead-Acid, Lithium, NiCad, etc.) For

details on how to do this, see Appendix 1.