Data sheet, Electrical specifications, General specifications – GE Industrial Solutions QBDW033A0B Barracuda Series User Manual

Page 3

Advertising
background image

GE

Data Sheet

QBDW033A0B Barracuda Series; DC-DC Converter Power Modules

36-75Vdc Input; 12.0Vdc, 33.0A, 400W Output

May 9, 2013

©2012 General Electric Company. All rights reserved.

Page 3

Electrical Specifications

(continued)

Unless otherwise indicated, specifications apply over all operating input voltage, resistive load, and temperature conditions.

Parameter

Device

Symbol

Min

Typ

Max

Unit

Output Voltage Set-point (Default)

(V

IN

=V

IN,nom

, I

O

=16.5A, T

A

=25°C)

(Adjustable via PMBus)

All V

O, set

11.97 12.00 12.03 V

dc

Output Voltage Variation from Default
(Over all operating input voltage (40V to 75V), resistive
load, and temperature conditions until end of life)

All w/o -

P

V

O

11.76

12.24

V

dc

-P

Option

V

O

11.63

12.37 V

dc

Output Voltage (V

IN

=36V, T

A

= 25ºC)

All

V

O

11.00

V

dc

Output Regulation [V

IN, min

= 40V]

Line (V

IN

= V

IN, min

to V

IN, max

) All

0.2

% V

O, set

Load (I

O

=I

O, min

to I

O, max

)

All w/o -

P

0.2

% V

O, set

Load (I

O

=I

O, min

to I

O, max

), Intentional Droop

-P

O ti

0.50

V

dc

Temperature (T

A

= -40ºC to +85ºC)

All

2

% V

O, set

Output Ripple and Noise on nominal output

(V

IN

=V

IN, nom

and I

O

=I

O, min

to I

O, max

)

RMS (5Hz to 20MHz bandwidth)

All

70

mV

rms

Peak-to-Peak (5Hz to 20MHz bandwidth)

All

200

mV

pk-pk

External Output Capacitance

For C

O

>5000uF, I

O

must be < 50% I

O, max

during T

rise

.

All C

O, max

0

10,000

μF

Output Current

All

I

O

0 33

A

dc

VOUT_OC_FAULT_LIMIT (Default)

(Adjustable via PMBus)

All I

O,lim

40

A

dc

Efficiency
V

IN

=V

IN, nom

, T

A

=25°C

I

O

=100% I

O, max,

V

O

= V

O,set

All

η

95.3

%

I

O

=40% I

O, max

to 75% I

O, max ,

V

O

= V

O,set

All

η

95.8

%

Switching Frequency

f

sw

150 kHz

Dynamic

Load

Response

dI

O

/d

t

=1A/10s; V

in

=V

in

,

nom

; T

A

=25°C;

(Tested with a 1.0μF ceramic, a 10μF tantalum, and
470μF capacitor and across the load.)

Load Change from I

O

= 50% to 75% of I

O,max

:

Peak Deviation
Settling Time (V

O

<10% peak deviation)

All

V

pk

t

s

__

500
700

__

mV

pk

s

Load Change from I

O

= 75% to 50% of I

O,max

:

Peak Deviation

Settling Time (V

O

<10% peak deviation)

All

V

pk

t

s

__

__

500

700

__

mV

pk

s

General Specifications

Parameter

Device

Symbol

Typ

Unit

Calculated Reliability Based upon Telcordia SR-332 Issue
2: Method I, Case 3, (I

O

=80%I

O, max

, T

A

=40°C, Airflow = 200

LFM), 90% confidence

All

MTBF

3,108,685

Hours

All FIT

321.7

10

9

/Hours

Weight – Open Frame

47.4 (1.67)

g (oz.)

Weight – with Base plate option

66.4 (2.34)

g (oz.)

Advertising