Data Sheet

November 29, 2010

PIM300X Series; ATCA Board Power Input Modules

-38 to -75Vdc ; 300W Input

LINEAGE

POWER

3

Absolute Maximum Ratings:

Stresses in excess of the absolute maximum ratings can cause permanent damage to the device. These are absolute
stress ratings only, functional operation of the device is not implied at these or any other conditions in excess of those
given in the operations sections of the data sheet. Exposure to absolute maximum ratings for extended periods can
adversely affect the device reliability.

Parameter

Device

Symbol

Min

Typ

Max

Unit

Input Voltage (Absolute values)

Continuous

All

V

I

0

-48

-75

Vdc

Transient (Pulse duration above

–75V = 1ms)

All

V

tr

-75

-100

Vdc

Temperature

Normal Operating Ambient Temperature
(See Thermal Considerations section)

All

T

A

-5

85

o

C

Storage Temperature

All

T

stg

-55

125

o

C

Power

Input Power, Maximum Allowable

All

P

in, max

300

W

Input to Output Voltage Differential
@ -48Vin & P

in,max

, T

A

=25

o

C

All

V

delta

0.8V

V

Efficiency
VIN=-48V, P

in,max

, T

A

=25

o

C (MGMT_PWR=0W)

All

η

98

%

Power Dissipation
(Internal Module Dissipation @ P

in, max

(with MGMT_PWR = 8W)

All

Pdiss

12

W

Output Power, Maximum Deliverable
(Management Power + Payload Power)

All

Pout

288

W

Management Power, Maximum Deliverable
(MGMT_PWR)

All

P

MGMT_PWR

8

W

Module Standby Power
(@-48Vin & MGMT_PWR=0W, Pout=0W)

All

P

Stdby

2.0

W

Isolation

Input to MGMT_PWR Output Voltage

All

1500

Vdc

Input to SHELF_GND Voltage

All

1500

Vdc

Input to LOGIC_GND Voltage

All

1500

Vdc

LOGIC_GND to SHELF_GND
Insulation Resistance with 100Vdc Test Voltage

All

9

MOhms

CAUTION: This power module is not internally fused. Both A & B feeds and their corresponding
returns must be individually fused.

To preserve maximum flexibility, internal fusing is not included. However, to achieve maximum safety and system
protection, the safety agencies require a fast-acting fuse with a maximum rating of 15 Amps and Voltage Rating >/=
75Vdc for the

–48AF, -48BF VRTN_AF & VRTN_BF feeds. Consult Fusing and fault protection (Section 4.1.4) of

PICMG 3.0 ATCA specifications for additional information. Based on the information provided in this data sheet on
inrush current and maximum dc input current, the same type of fuse with a lower rating can be used. Refer to the
fuse manufacturer’s data sheet for further information.