Operating Manual ADVANCED SNMP WEB INTERFACE CARD

8.2.5 Test web page

Clicking on the “Test” page link a similar screen will appear:



Meaning of the different fields shown at the UPS Tests page:

Test Group

Test ID:

Shows the name of the test in progress if a test is in progress or the name of the last test

performed, if no test is in progress, unless no test has been run, in which case the value
NoTestsInitiated is returned.

Test Result
Summary:

The results of the current, or last UPS diagnostics test performed.
The values for donePass,doneWarning, and doneError indicate that the test was completed
either successfully, with a warning, or with an error, respectively.

The value aborted is returned for tests which are aborted by setting the value TestInit to
AbortTestInProgress.
Tests which have not yet concluded are indicated by inProgress.
The value noTestsInitiated indicates that no previous test results are available, such as is
the case when no tests have been run since the last reinitialization of the network

management subsystem and the system has no provision for non-volatile storage of test
results.

Test Init:

Gives the possibility to choose between four different actions that the UPS could perform:
QuickBatteryTest:

A test sufficient, to determine if the battery needs replacement.

Abort Test In Progress:

The test in progress has to be aborted.

GeneralSystemTest:

The manufacturer's standard test of UPS device systems.

DeepBatteryCalibration:

The system is placed on battery to a discharge level, set by the
manufacturer, sufficient to determine battery replacement and
battery run-time with a high degree of confidence.


WARNING:

this test will leave the battery in a low charge state and will require time

for recharging to a level sufficient to provide normal battery duration for

the protected load.


NOTE:

Only after clicking in the “Apply” button the UPS starts to perform the
action
.