8.2.7 Configuration web page

Clicking on the “Configuration” page link a similar screen appears:


Meaning of the different fields present at the UPS Configuration page:

Configuration Group

Input Voltage:

The magnitude of the nominal input voltage.

Input Frequency:

The nominal input frequency.

Output Voltage:

The magnitude of the nominal output voltage.

Output Frequency:

The nominal output frequency.

Low Battery Time:

The value of EstimatedMinutesRemaining (see page “UPS Details”) at which a

lowBattery condition is declared.

Low Voltage Transfer
Point:

The minimum input line voltage allowed before the UPS system transfers to battery
backup.

High Voltage Transfer
Point:

The maximum line voltage allowed before the UPS system transfers to battery
backup.

Audible Status:

The requested state of the audible alarm.
When in the disabled state, the audible alarm should never sound.

The enabled state is self-describing.

Setting this object to muted when the audible alarm is sounding shall temporarily
silence the alarm. It will remain muted until it would normally stop sounding and the

value returned for read operations during this period shall equal muted.
At the end of this period, the value shall revert to enabled.

Writes of the value muted when the audible alarm is not sounding shall be accepted
but otherwise shall have no effect.

Output VA:

The magnitude of the nominal VA rating.

Output Power:

The magnitude of the nominal true power rating.