GE

Data Sheet

12A Digital SlimLynx

TM

Open Frame: Non-Isolated DC-DC Power Modules

3Vdc –14.4Vdc input; 0.45Vdc to 5.5Vdc output; 12A Output Current

February 19, 2014

©2014 General Electric Corporation. All rights reserved.

Page 23


where I

OUT_CORR

is the temperature corrected value of the

current measurement, I

READ_OUT

is the module current

measurement value, T

IND

is the temperature of the inductor

winding on the module. Since it may be difficult to measure
T

IND

, it may be approximated by an estimate of the module

temperature.

Measuring Output Voltage Using the PMBus

The module can provide output voltage information using
the READ_VOUT command. The command returns two bytes

of data all representing the mantissa while the exponent is
fixed at -10 (decimal).

During manufacture of the module, offset and gain
correction values are written into the non-volatile memory of
the module. The command VOUT_CAL_OFFSET can be used

to read and/or write the offset (two bytes consisting of a 16-
bit mantissa in two’s complement format) while the
exponent is always fixed at -10 (decimal). The allowed range

for this offset correction is -125 to 124mV. The command
VOUT_CAL_GAIN can be used to read and/or write the gain
correction - two bytes consisting of a five-bit exponent (fixed
at -8) and a 11-bit mantissa. The range of this correction
factor is -0.125V to +0.121V, with a resolution of 0.004V. The
corrected output voltage reading is then given by:

OFFSET

CAL

VOUT

GAIN

CAL

VOUT

Initial

V

Final

V

OUT

OUT

_

_

)]

_

_

1

(

)

(

[

)

(

+

+

×

=

Measuring Input Voltage Using the PMBus

The module can provide output voltage information using
the READ_VIN command. The command returns two bytes of
data in the linear format. The upper five bits [7:3] of the high
data form the two’s complement representation of the

exponent which is fixed at –5 (decimal). The remaining 11 bits
are used for two’s complement representation of the
mantissa, with the 11

th

bit fixed at zero since only positive

numbers are valid.

During module manufacture, offset and gain correction
values are written into the non-volatile memory of the
module. The command VIN_CAL_OFFSET can be used to
read and/or write the offset - two bytes consisting of a five-

bit exponent (fixed at -5) and a11-bit mantissa in two’s
complement format. The allowed range for this offset
correction is -2 to 1.968V, and the resolution is 32mV. The

command VIN_CAL_GAIN can be used to read and/or write
the gain correction - two bytes consisting of a five-bit
exponent (fixed at -8) and a 11-bit mantissa. The range of

this correction factor is -0.125V to +0.121V, with a resolution
of 0.004V. The corrected output voltage reading is then given

by:

OFFSET

CAL

VIN

GAIN

CAL

VIN

Initial

V

Final

V

IN

IN

_

_

)]

_

_

1

(

)

(

[

)

(

+

+

×

=

Reading the Status of the Module using the PMBus

The module supports a number of status information
commands implemented in PMBus. However, not all

features are supported in these commands. A 1 in the bit
position indicates the fault that is flagged.

STATUS_BYTE : Returns one byte of information with a
summary of the most critical device faults.

Bit

Position

Flag

Default

Value

7 X 0
6 OFF 0
5 VOUT

Overvoltage 0

4 IOUT

Overcurrent 0

3 VIN

Undervoltage 0

2 Temperature 0
1

CML (Comm. Memory Fault)

0

0

None of the above

0

STATUS_WORD : Returns two bytes of information with a
summary of the module’s fault/warning conditions.

Low Byte

Bit

Position

Flag

Default

Value

7 X 0
6 OFF 0
5

VOUT Overvoltage

0

4 IOUT

Overcurrent 0

3 VIN

Undervoltage 0

2 Temperature 0
1

CML (Comm. Memory Fault)

0

0

None of the above

0

High Byte

Bit

Position

Flag

Default

Value

7

VOUT fault or warning

0

6

IOUT fault or warning

0

5 X 0
4 X 0
3

POWER_GOOD# (is negated)

0

2 X 0
1 X 0
0 X 0