Safety, Safety statements – GE Industrial Solutions 664 Infinity C DC to DC Power System User Manual

Page 11

Advertising
background image

663 / 664E Installation Guide

CC848921016 r02 December 2012

Page 11

Safety

Safety Statements

Read and follow these statements and those in equipment manuals.
• Do not install this equipment over combustible surfaces.

• Follow all national and local rules and regulations when making field connections.

• Compression Connectors

• For installations in the U. S. or Canada, use Listed/Certified compression connectors to terminate

Listed/Certified field-wire conductors where required.

• For all installations, apply the appropriate connector to the correct size conductor as specified by the

connector manufacturer, using only the connector manufacturer’s recommended or approved tooling for that

connector.

• If the proper connector for the country of installation is not provided, obtain appropriate connectors and follow

manufacturer’s requirements and all local requirements for proper connections.

• Torque electrical connections to the values specified on labels or in the product documentation.

• Dress cables to avoid damage to the conductors (caused by routing around sharp edges or routing in areas

where wires could get pinched) and undue stress on the connectors.

• Size protectors (fuses or circuit breakers) as required by the National Electric Code (NEC) and/or local codes. Refer

to the equipment ratings to assure current does not exceed:

Continuous Load (List 1) - 64% of protector rating

Maximum Load (List 2 - typically end of discharge) - 80% of protector rating.

• Field-wired Conductors - Follow all National Electric Code (NEC) and local rules and regulations when making field

connections.

• Size field-wired conductors based on listed recommendations, National Electric Code (NEC) and/or local codes

based on 70°C ampacity.

• Insulation rating: 90°C minimum; 105°C (minimum) if internal to enclosed equipment cabinets.

• Provide an accessible AC disconnect/protection device to remove AC power from the equipment in the event of an

emergency. This device must open all poles and be connected together.

• Equipment and subassembly ports are suitable for connection to intra-building or unexposed wiring or

cabling. The equipment and subassembly ports can be connected to shielded intra-building cabling

grounded at both ends.

• Alarm contacts are not fused within the equipment. Current limiting protection for these contacts must

be provided by external circuits. Exceeding these maximum ratings could result in fire or damage to the

unit. Alarm contacts are rated at 60V and 0.5A unless otherwise noted in the product Specifications

section.

• In enclosed equipment cabinets, the equipment chassis must be connected directly to the cabinet ac

service ground bus. For applications in huts, vaults, and central offices, the equipment chassis must be

connected to the system bonding network.

• Use only fuses and circuit breakers specified in the equipment documentation. Use of other parts may

result in injury to personnel or equipment damage.

• Use only GMT fuses provided with safety caps.

• This equipment operates equally well if installed as part of the Isolated Ground Plane (Isolated Bonding Network) or

the Integrated Ground Plane (Mesh-Bonding Network, aka, Common Bonding Network). Different grounding

techniques are equally successful. Adhere to a commonly accepted and consistent grounding approach to ensure

personnel safety, network protection, and proper equipment operation. Multiple low impedance paths to Earth

ground are essential.

Advertising