Enable and Program the TFD and FVS Systems

The TFD and FVS systems must be enabled.
+

Set the pump for mode 0. Press the MODE button until MODE 0 is
shown on the LCD display.

A-100NE

Page 12

+

Press the DIGIT button to set the number of seconds of alarm delay time.
The number will increase to a maximum of 256 seconds and roll over to
OFF.

+

To exit the programming mode, press the RUN/STANDBY button and the
MODE button at the same time. The arrow next to the word

PROGRAM

will disappear and an arrow will appear next to the word

RUN.

NOTE: If while in the program mode no buttons are pressed within 60
seconds, the circuitry will automatically return to the run mode.

+

Enter the programming mode. At the same
time, press the RUN/STANDBY button and
the MODE button. A blinking

ARROW will

point to the word

PROGRAM indicating the

program mode has been activated. The

TFD

icon will blink. The word

ON will display

indicating the TFD system is activated.

+

Press the DIGIT button to toggle the system
on and off.

+

Press the MODE button to enter the FVS
system programming. The

FVS icon will

blink. The display will indicate the current
alarm delay time setting in seconds. (000 =
OFF.

RUN

PROGRAM

STAND-BY

PRIME

MINIMUM

MAXIMUM

0

On

MODE

TFD

RUN

PROGRAM

STAND-BY

PRIME

MINIMUM

MAXIMUM

0

001

MODE

FVS

SEC

6.3 Mode 1 - Manually adjusting the output

- In this mode, the pump

is turned on and off by an electronic cycle timer. The pump will energize for
the duration of the “on time” and de-energize for the remainder of the “total
time” thus completing one cycle. The cycle then repeats.
The “on time” and “total time” cycles are independently adjustable from 0.1
to 199.9 units of measure with a 0.1 unit resolution. The units of measure
can be seconds, minutes, hours or days.
Example: If the “total time” cycle is adjusted for 90 seconds and the “on
time” portion of the cycle is adjusted for 5 seconds, the pump will run for 5
seconds and turn off for 85 seconds (90 second total cycle). This cycle is
repeated until either the standby button is pressed, the cycle time is changed
or the input power is disconnected from the pump.
+

Set the pump for mode 1. Press the MODE button until MODE 1 is
shown on the LCD display.