Installation & Maintenance Manual

2000 BRAY CONTROLS

Page 21 of 24

Figure 9: Example of setting an EDS parameter

4. Trouble Shooting

4.1 Calibration

1. Verify that the Series 70 CAMS are correctly set (Section 2.4) and are engaged when

the Open Limit and Close Limit are reached.

2. Verify that the Feedback Pot (Section 2.2.4), connector J4 is connected and oriented

correctly.

3. If the Calibration still fails, ensure that the S70 has been properly wired to the Series 70

Actuator. Review Section 2.2 for proper connector wiring and then repeat from step 3
above.