Ardware, Eatures, Onnector – Bray 70 Series SERVO PRO DeviceNET User Manual

Page 5: Iring, S70 actuator motor connector

Advertising
background image

S70 DeviceNet Servo

Installation & Maintenance Manual

2000 BRAY CONTROLS

Page 4 of 24

2.1 Hardware Features


The following are standard hardware features of the S70 DeviceNet Servo:

DeviceNet 5-position open style connector
S70 Actuator Motor connector
S70 Actuator Limit Switch connector
Feedback Potentiometer connector
Red and green calibration LED indicators
Green Power LED
Green Motor Running Open drive LED
Red Motor Running Closed drive LED
Bi-color (red / green) DeviceNet Network Status LED

2.2 Connector Wiring

2.2.1 S70 Actuator Motor Connector


The S70 Actuator Motor is connected to the S70 DeviceNet Servo motor power terminal
connector with 3 wires: Common (Black Wire), Motor Open (Blue Wire), and Motor Close (Red
Wire).

2.2.2 S70 Limit Switch Connector


If any of the Series 70 features such as the Handwheel switch (Auto / Manual Operation), torque
limit switches, or limit switches (open limit and close limit) are not used, they must be connected
to

a terminal labeled “common” for the S70 to operate.

Description

Electrical Notes

Feature Availability

Auto / Manual Handwheel
Actuator Operation

Auto Operation = Low
Manual Handwheel Engaged = Open

Standard

Closed Torque Limit

Normal Operation = Low
Limit Reached = Open

Standard

Open Travel Limit

Normal Operation = Low
Limit Reached = Open

Standard

Closed Travel Limit

Normal Operation = Low
Limit Reached = Open

Standard

Open Torque Limit

Normal Operation = Low
Limit Reached = Open

Standard

Table 1: Limit Switch Connector J6 pin description

Advertising