24 configuration, Fault indicator – MoTeC PDM30 User Manual

Page 27

Advertising
background image

24

Configuration

to protect the wire from overheating, not to protect the connected
device.

Some devices draw more current under circumstances such as high or

low battery voltage. Also, a motor will draw increased current when
under more load. Set a good margin and where possible check the
Output Load value under these varying circumstances.

Configuration of an output will create a number of channels, some of which
are transmitted via CAN. OutputName.Status channel is used for output
status information on CAN. The output should be on for any non-zero value.

Channel Name

Description

CAN
Output

OutputName

Output Control Status
0 = Off
1 = On (Note: the output may be off
due to Over-current Shutdown or
Fault Shutdown)

No

OutputName.Voltage

Voltage on the output
Resolution 0.2 V

Yes

OutputName.Current

Output Current in amps
Resolution 0.5 A on Outputs 1

– 8

Resolution 0.2 A on Outputs 9

– 32

Yes

OutputName.Load

Output Load. Filtered current as a
percentage of the maximum current
setting.
Resolution 1%

Yes

OutputName.Status

0 = Off
1 = On Active
2 = Over-Current Shutdown
4 = Fault Shutdown

Yes

OutputName.Status.
Active

0 = Output is off
1 = Output is on

No

OutputName.Status.
OverCurrent

0 = OK
1 = Over-Current Shutdown

No

OutputName.Status.
Fault

0 = OK
1 = Fault Shutdown

No

Fault Indicator

When an output fault occurs the PDM sets the value of the Global Error
channel to TRUE (PDM.Global Error). A fault indicator light can be connected