Each refrigeration system is mounted on a galvanized steel skid, and is completely self contained. It

contains the following:

High Pressure Switch

The high pressure switch is a manually resetting, totally encapsulated switch that is mounted on a

Schrader valve connection. If the switch requires replacement it can be unscrewed from the piping

system without loss of refrigerant. In the event of a high pressure switch failure, the switch must be

manually reset by pressing the red button. It will close when the system head pressure is below the

switch cut-in pressure. The controller must then be reset.

Low Pressure Switch

The low pressure switch is a automatically resetting, totally encapsulated switch that is mounted on

a Schrader valve connection. If the switch requires replacement it can be unscrewed from the piping

system without loss of refrigerant.

When the suction pressure drop below the cut out value, the compressor will shut off after a short

time delay. At compressor startup there is a starting time delay that ignores and open low pressure

switch to allow suction pressure to be built up. If the suction pressure does not build up fast enough,

the time delay can be increased.