Schreiber Chillers 1055 New User Manual

Page 37

Advertising
background image

Sets and displays the main temperature setpoints.

DISCHARGE SETPOINT

DISCHARGE: The setpoint for the chilled water reservoir. This temperature will be delivered

through both pump loops.

HIST: This is the differential around the setpoint of which the system will cycle. HIST =

Histeresis.

A 50 F setpoint with a 1.0F differential means the system will turn on at 51 F and shut off at 49

F.

LOOP 2 SETPOINT

TEMP RISE: The difference in temperature of loop 2 (GCHE/GAHE loop) above the discharge

temperature which signals the second compressor to become active.

HIST: The differential around which the second compressor goes active/inactive.

Example:

§

Discharge Temp: 50F +/_ 1.0 F

§

Temp Rise: 10 F +/- 2 F.

§

Both pumps are and both compressors are enabled.

Operation:

• Compressor 1 cycles on at 51 and off at 49.

• A scan is started.

• Return temperature of loop 2 begins to rise.

• Return temperature reaches 62 F (50 + 10 + 2), compressor 2 goes active.

• Discharge Temperature now climbs to 51 F.

• Both compressors now cycle (separated by a short delay).

• Compressors pull tank temperature down to 49 F and cycle off.

• Scanning stops, retrun temperature drops below 58 (50 + 10 –2).

Compressor 2 returns to standby.

HIGH TEMPERATURE ALARM SETPOINT

SET: Sets and displays the high temperature alarm setpoint.

HIST: The differential around the setpoint which the alarm will operate.

ENABLED: Displays whether or not the high temperature alarm is enabled.

ROTATION

ENABLED/DISABLED. This controls whether or not compressor rotation will take place. When

both compressors are enable at the main ON/OFF screen, rotation mode can be selected to

be enabled or disabled. When one or of the compressors is disabled, then the controller will