Setpoints –

The customer can change this setting based on their requirement.

Temp Rise: 10.0

0

F

Hist: 01.0

0

F

High Temp Alarm –

The customer can change this setting based on their requirement.

Set: 85.0 0F

Hist: 05.0 0F

Disable

/

Enable

Rotation

Status: AUTO

FOR / REV

Enable: Yes / No


RUN HOURS

Run Hours

Pump 1:

00000000000

Comp

1:

00000000000

Liquid1: 00000000000

Run Hours

Pump

2: 00000000000

Comp

2:

00000000000

Liquid2: 00000000000

Run Hours

Fans:

00000000000


THESE VALUES WILL CHANGE WHEN SYSTEM IS RUNNING


FACTORY SETTINGS:

PASSWORD PROTECTED: 0177

Pumps #1 SETTINGS

Minimum On:

000 s

Minimum

Off:

000

s

Flow Start Del:

05 s

Pumps #2 SETTINGS

Minimum On:

000 s

Minimum

Off:

000

s

Flow Start Del:

05 s

Comp #1 SETTINGS

Minimum On:

010 s

Minimum

Off:

060

s

Comp #2 SETTINGS

Minimum On:

010 s

Minimum

Off:

060

s

Circuit #1 SETTINGS

Low P Start Del: 30 s

Circuit #2 SETTINGS

Low P Start Del: 30 s

Condenser Fan Config

Minimum On: 010 s