Schreiber Chillers 1055 New User Manual

Page 42

Advertising
background image

Minimum Off: 010 s

Fan Control – Head Pressure Control

Setp:

190

Band:

030

Vspeed: ENABLE

/

DISABLE

Min Freq: 030

Max: 060

Condenser Fan Config

VFD minimum: 000 Hz

VFD Maximum: 065 Hz

Factory Settings

Temperature Unit:

0

F

Pressure Units: PSI Changing this parameter will not display correct reading in BAR

Password Maintenance

Factory Pass: 0177

Supervisor setup

Ident:

001

Baud:

1200

Protocol:

n/a

Unit Configuration

Evap

Sensors:

No

Voltage

Monitor:

Yes

Misc Settings

Tiem Betw Comps: 010 s

Screen Saver Delay: 005 min

Serial No

Change Serial No on the Chiller

Hi Temp Alarm

Enable: Yes

ALARM HISTORY

THIS DISPLAYS THE LAST 20 ALARM FAULT CODES.


DATE AND TIME

Date / Time Settings:

THIS SETS THE CURRENT DATE AND TIME

SENSOR CALIBRATION

Head Pressure #1

Current:

Current head pressure reading

Off set:

00 psi offset value

Min: 000 Psi

Max: 415

Head Pressure #2

Current:

Current head pressure reading

Off set:

00 psi offset value

Min: 000 Psi

Max: 415

Discharge Temp