Water Treatment

Water quality is of the utmost importance for the proper
care and maintenance of the modular chiller system.
Proper water treatment is a specialized industry and we
recommend consulting an expert in this fi eld to analyze the
water for compliance with the water quality parameters
listed in Table 1. The material used in the ClimaCool chiller
exposed to the water are type 316 stainless steel, pure
copper, and carbon steel. Other materials may exist external
to the ClimaCool chiller. It is the user’s responsibility to
ensure these materials are compatible with the treated
water. Regular treatment of the water will increase
longevity of your system. Failure to provide adequate
fi ltration or treatment of evaporator water will void the
ClimaCool module’s warranty.

Heavy-Contaminated Water

In such instances whereby the particulates in the water are
excessive it is recommended to install an intermediate plate
& frame heat exchanger to isolate the ClimaCool chiller from
the building water system.

*(<;065

t &YDFTTJWF$IMPSJOF 6OEJTTPMWFE4PMJETBOE

PUIFSJNQSPQFSXBUFSRVBMJUZDPOEJUJPOT

WILL DAMAGEUIFJOUFSOBMIFBUFYDIBOHFSBOE

WILL VOID YOUR WARRANTY!

Table 1 - Water Quality Parameters

WATERCONTAINING

CONCENTRATION

Ammonia

Lessthan2.0mg/l

CaCO3Alkalinity

30Ͳ500mg/l

CaCO3Hardness

30Ͳ500mg/l

Chlorides

Lessthan200mg/l

DissolvedSolids

Lessthan1000mg/l

Iron

Lessthan5.0mg/l

Manganese

Lessthan0.4mg/l



Nitrate

Lessthan100mg/l

pH

7.0Ͳ9.0

Sulphate

LessThan200mg/l