Caution: Do not charge to achieve subcooling temperature when the TXV is overfeeding. If the TXV is overfeeding,
readings may still indicate low subcooling and low superheat, but circuit may not be undercharged.

Run

Compressor

for 5 Minutes

Is Superheat

in Range?

Yes

No

Is Subcooling

in Range?

Yes

No

Is Superheat

Low or High?

High

Low

Turn TXV

Adjustment

Stem Clockwise

Is Subcooling

Low or High?

High

Low

Add Refrigerant

Is Subcooling

Low or High?

High

Low

Recheck Superheat

and Complete

Start-up and

Warranty Form

Add Refrigerant

Remove

Refrigerant

Turn TXV

Adjustment Stem

Counter Clockwise

Startup Documentation

All startup paperwork and documentation must be submitted to ClimaCool. Future warranty claims cannot be processed
without a completed Startup and Warranty Registration form on fi le (See page 43).