Troubleshooting guide – ClimaCool SHC onDEMAND 30, 50, 70, 85 Manual User Manual

Page 60

Advertising
background image

www.climacoolcorp.com

58

Troubleshooting Guide

WARNING!
The troubleshooting guidelines recommended in this section
could result in exposure to electrical safety hazards. Please
refer to the safety warnings provided in this manual. Failure
to follow all of the recommended safety warnings provided
could result in death or serious injury. When possible,

Š‹ŽŽ‡”‹ŽŽ‘––ƒ”–

‘••‹„Ž‡ƒ—•‡

‡‡†›

Power off

Check main disconnect switch

Main line open

Check main fuses

Incorrect wiring

Check the wiring diagram

Loose terminals/connections

Tighten the terminal connections

Control circuit open

Check interlocks with auxiliary equipment, pressure and
temperature controls

Improper phasing of main power

Change any two of three phases of main power

‘’”‡••‘” —•—–‘‡•‘––ƒ”–

‘••‹„Ž‡ƒ—•‡

‡‡†›

Low voltage

Check at main power entry and unit power entry (consult power
company if low)

Phase loss

Check power wiring and fuses

‘’”‡••‘”—•—–‘‡•‘–‘‘Ž

‘••‹„Ž‡ƒ—•‡

‡‡†›

Improper phasing of main power

Switch any two of three phases of main power

‘’”‡••‘”—–•—–‘™”‡••—”‡ƒˆ‡–›‘–”‘Ž

‘••‹„Ž‡ƒ—•‡

‡‡†›

Main chilled water valve closed or restricted Open

valve

to

full

open

position

Module chilled water isolation valves, if
provided, closed or restricted

Open valves to full open position

Refrigerant storage

Check for leaks Ȃ add refrigerant

No load on water chiller

Check water pump operation

Restriction in liquid line

Plugged liquid line drier Ȃ replace liquid line drier

Expansion valve clogged or inoperative Repair/replace

the

expansion

valve

Low discharge pressure

Raise and control discharge pressure within design limits

Low water flow through the cooler

Check water flow through the cooler

Chilled water temperature too cold

Raise water temperature setpoint

Fouled evaporator brazed plate heat exchanger

Clean-in-place heat exchanger as described in IOM (page 31)

Improper chilled water circulation

Use an ample sized cleanable strainer in the chilled water circuit;
make certain the strainer is clean to insure full flow of chilled
water (strainer screen must be 60 mesh minimum)

Faulty suction pressure transducer

Verify transducer calibration using a calibrated manifold gauge
and replace if defective

Wrong suction pressure cutout setpoint

Verify suction pressure cutout setpoint to be set equal to the
corresponding leaving chilled solution freeze temperature
equivalent pressure on a PT chart. (i.e. If the solution freeze point
is 32

o

F, the equivalent pressure setpoint will be 101 psig.)

disconnect all electrical power including remote disconnects
before servicing. Follow proper lockout-tagout procedures.
Ž›ƒ“—ƒŽ‹Ƥ‡†Ž‹…‡•‡†‡Ž‡…–”‹…‹ƒ‘”’‡”•‘•–”ƒ‹‡†–‘
handle live electrical components should only be allowed
to work with energized electrical components.