ClimaCool offers two types of water header bypass kits, direct

return (Figure 6) and reverse return (Figure 7) as shown on

page 10 . The bypass kits must be installed on each water source

loop and controls are integrated with the CoolLogic software .

Installation location can be found on page 12 – Water Piping

Configuration.

This bypass can also be created with field supplied piping. The

design piping must accommodate one module’s worth of design

flow, and be positioned so that the temperature and differential

flow sensors sense active flow in the bypass mode. See Figures

9 and 10 on page 12 - Water Piping Configuration. The field

supplied piped chiller/heater system bypass must be controlled

by others. There are system communication delays, polling and

network conflicts that strictly prohibit the use of ClimaCool

sensors and controls for control of field supplied bypasses or

other field supplied items. Recommended method is to control

via differential pressure or gpm flow meters across the chilled

water/evaporator, hot water/condenser water systems .

LOAD 1

FROM CHILLER BANK

TYPICAL LOAD BYPASS VALVE ARRANGEMENT

TO CHILLER BANK

LOAD 2

LOAD 3

LOAD X

TYPICAL CHILLED AND HOT WATER

LOAD SIDE BYPASS VALVES

SIZE EQUIVALENT TO ONE MODULE

WORTH OF FLOW

Figure 8 - Typical Load Bypass Valve Arrangement

Load Side System Bypass (Air Handlers, Fan

Coils, etc.)

A load system bypass is required for preventing pump

deadheading, allowing active flow system sensing and

preventing starving flow from the chiller/heater system.

Examples of an acceptable load side system bypass are:

•Utilize a quantity of 3-way control valves on the largest

loads farthest from the chiller/heater system .

•Field piping with a control valve to provide a bypass across

the larger system loads when their 2-way valves go closed .

Please refer to Figure 8 for a typical load bypass

valve arrangement . The load side system bypass should be

sized for an absolute minimum of one module’s worth of

design flow. (Please refer to selection submittals for design

flow rates). A minimum of (6) six gallons per nominal system

ton are also required to maintain proper system thermal

inertia . This is to avoid short cycling of compressors in the

chiller/heater system as well as prevent nuisance alarms .