Troubleshooting for atf package, Auxiliary contacts, Water resistance – ClimaCool UCW_H 30, 50, 70, 85 User Manual

Page 45

Advertising
background image

43

www.climacoolcorp.com

When the differential set point is reached both the audible

and visual alarms will be triggered and will remain engaged

until both the alarm condition is corrected and the

alarm-reset button is pressed (if the alarm-reset button is

pressed but the differential pressure is beyond the set point,

the alarms will re-engage immediately) . After the strainer

is cleaned and put back in service, the differential pressure

should return to 1 psi .

Auxiliary Contacts

The PDA option is equipped with a remote alarm feature .

The remote alarm contacts are located at the two black and

red banana clip posts (See Figure 21) . The alarm can be set

up in one of two ways:

1. A remote alarm signal of 12 VDC can be sent to a central

monitoring station or

2. A set of auxiliary contacts will indicate a “closed”

condition when the alarm activates . (Locate the

Auxiliary Contact Schematic inside the PDA box by

removing the four screws on the cover plate) .

Water Resistance

The Pressure Differential Alarm Controller is water-resistant,

but not water proof . Do not install below ground level

where the box can be submerged in water . Do not remove

the cover plate from the PDA controller . Keep the cover

tightly sealed on the module during normal operation .

Problem

• Seals damaged or worn out

• Install repair kit

• Valve is not stopping at proper closed position

• Adjust limit switches

Valve stem leaks

• Worn stem seals

On metal valves: tighten stem packing nut 1/2 turn.
CAUTION! Over tightening stem nut could cause drag on
motor and trip internal circuit breaker. May require repair kit
or new valve.

• Loose body bolts or excessive operation pressure

• Check bolts and observe recommended pressure ratings

• Defective seals

• Install repair kits or new valve

• Swollen seals or product buildup in valve chamber

• Check valve for compatibility with product, may require valve

cleaning or new valve

• Valve bolts too tight

• Loosen bolts slightly

• Stem nut too tight

• Loosen stem nut slightly

Troubleshooting for ATF Package

Solution

Valve is leaking past ball

Valve hard to turn

Valve body leaks

Table 3

Advertising